CAUTION
•
If the diameter of the connection hose is smaller than
the product's drain hose, leakage may occur.
Drain hose (A)
1.57~1.97inch(40~45mm)
Drain hose
Vinyl tape
4
Do not box in or cover the drain hose connection. It must
be accessible for testing later in the installation process
and for future servicing.
5
If the drain hose is routed inside the room, insulate the
hose so that dripping condensation does not damage the
furniture or floors.
Extension drain hose (B)
40~45 mm
(A)
(B)
Extension drain hose
0.79inch (20mm) or more
Foam insulation
Step 10 Connecting the power and
communication cables
CAUTION
•
Always remember to connect the refrigerant pipes
before performing the electric connections.
When disconnecting the system, always disconnect the
electric cables before disconnecting the refrigerant
pipes.
•
Always remember to connect the air conditioner to
the grounding system before performing the electric
connections. Use a crimp ring terminal at the end of
each wire.
The indoor unit is powered through the outdoor unit by means
of a H05 RN-F connection cable (or a more power model), with
insulation in synthetic rubber and a jacket in polychloroprene
(neoprene), in accordance with the requirements specified in
the standard EN 60335-2-40.
1
Remove the screw on the electrical component box and
remove the cover plate.
2
Route the connection cord through the side of the indoor
unit and connect the cable to the terminals refer to the
figure below.
3
Route the other end of the cable to the outdoor unit
through the ceiling & the hole on the wall.
4
Reassemble the electrical component box cover, carefully
tightening the screw.
English
11