Samsung AC BNADCH Series Installation Manual page 12

Hide thumbs Also See for AC BNADCH Series:
Table of Contents

Advertisement

Indoor Unit Installation
Indoor Unit
1(L) 2(N)
Outdoor
Unit
1(L) 2(N) L
Main power cable
Indoor Power
Indoor power supply
Max/
Power supply
Min(V)
±10%
208 to 230V, 60Hz
Communication cable
0.0012in² ↑(0.75mm²↑), 2 wires
12
English
F1
F2
Cable clamp
N
F1 F2
Cable
Tie
Cable
clamp
Communication cable
Indoor power cable
0.0012in² ↑(0.75mm²↑),
3 wires
AC power, Communication : M4 screw
1(L)
2(N)
0.54(13.8)
0.41(10.3)
N‧m
M3.5
0.8 to 1.2
M4
1.2 to 1.8
(1N‧m=10kgf‧cm)
Power supply cords of parts of appliances for outdoor use
shall not be lighter than polychloroprene sheathed flexible
cord. (Code designation IEC:60245 IEC 57 / CENELEC:
H05RN-F)
Since it has the external power supply, refer to the
outdoor unit installation manual for MAIN POWER.
CAUTION
When installing the indoor unit in a computer room or
network room, use the double shielded communication
cable (tape aluminum / polyester braid + copper) of
FROHH2R type.
(Unit: inch (mm))
F1
F2
Tightening torque
lbf.ft
0.59 to 0.89
0.89 to 1.1

Advertisement

Table of Contents
loading