Download Print this page

INTEGRA Metering AMTRON S3 Installation And Operating Instructions Manual page 18

Compact heat meter compact heat/cooling meter compact cooling meter

Advertisement

Available languages

Available languages

5) Maximum temperature
difference
alternating with date
and time
Level 5 / Parametrizing Loop:
1) Parametrizing
„unit of energy"
8.1 Parametrizing loop
a) The following characteristics of the meters can be set on location, only once, by pushing the button or
alternatively using the „Device Monitor" software:
-
unit of energy (kWh; MWh; GJ; MMBTU; Gcal)
-
installation point (inlet flow; outlet flow).
These parametrizing options are only available when the amount of energy is still <= 10 kWh. Make sure that
these characteristics are set as needed before starting up the system.
Setup by pushing the button: In order to start the editing mode for parametrizing you must select the respective
item in the parametrizing loop and then push the button once again for 2-3 seconds. As an aid, after 2 seconds the
„editing pen" will be displayed bottom left in the LCD (see below picture). As soon as it appears you have to let go
of the button. Then the current display will start blinking.
By pressing the push-button briefly you can switch to the next option. By pressing the push-button longer the
currently displayed option will be set. If no option is chosen there will be no change and as soon as the LCD goes
out the edit mode will end automatically.
b) The following characteristic of those mechanical meter types designed to be used with glycol can be set on
location at any time using the „Device Monitor" software:
-
type and concentration of glycol in the medium (propylene glycol; ethylene glycol; 20 %; 30 %; 40 %; 50%).
8.2 Detection of flow
As long as the meter detects some flow the following pictogram will be displayed bottom right in the LCD.
flow detected
9 Application Conditions
AMTRON
S3 / AMTRON
®
Maximum flow qs/qp
Mechanical class
Page 18 of 37
Article no.: 1080621015
2) Parametrizing
„installation point"
S3+ / AMTRON
S3U
®
®
2:1
M2
2022_01_18
Subject to technical change! Errors excepted.

Advertisement