4.3.3

Semi-flush mounting protection relay

A mounting kit is needed for semi-flush mounting the protection relay. In addition
to the detailed mounting instructions, the mounting kit includes:
• Raising frame
• Gasket
• Screws
Requirements for installation:
• Panel cut-out of 165.5 × 161.5 mm with mounting holes
• Depth behind the panel 103 mm
• When IP 54 degree of protection (according to IEC 60529) is required for the
front side, a gasket has to be used in the installation.
615 series
Installation Manual
A
C
177 mm
177 mm
164 mm
201 mm
D
E
G
E
153 mm
F
48 mm
G
160 mm