Standard Functional Module, Fm 200 - Grundfos CMBE 1-44 Installation And Operating Instructions Manual

Table of Contents

Advertisement

6.2 Standard functional module, FM 200

6.2.1 Inputs and outputs
The module has these connections:
two analog inputs
two digital inputs or one digital input and one
open-collector output
Grundfos Digital Sensor input and output
two signal relay outputs
GENIbus connection.
All inputs and outputs are internally separated from
the mains-conducting parts by reinforced insulation
and galvanically separated from other circuits. All
control terminals are supplied with protective extra-
low voltage (PELV), ensuring protection against
electric shock.
6.2.2 Signal relay 1
LIVE: You can connect supply voltages up to 250
VAC to the output.
PELV: The output is galvanically separated from other
circuits. Therefore, you can connect the supply
voltage or protective extra-low voltage to the output
as desired.
6.2.3 Signal relay 2
PELV: The output is galvanically separated from other
circuits. Therefore, you can connect the supply
voltage or protective extra-low voltage to the output
as desired.
6.2.4 Connection terminals for the mains supply
Phases
Terminals
Single-phase
N, PE, L
Three-phase
L1, L2, L3, PE
10
6.2.5 Connection terminals for inputs and outputs
DANGER
Electric shock
Death or serious personal injury
Make sure that the wires to be connec-
ted to the connection groups below are
separated from each other by rein-
forced insulation in their entire lengths.
OC
+24 V*
GND
+24 V*
+24 V*
+24 V*/5 V*
+
+
+24 V*
+24 V*
+24 V*/5 V*
Connection terminals, FM 200
* If you use an external supply source, there must be
a connection to GND.
NC
C1
NO
NC
C2
NO
DI
10
DI3/OC1
4
AI1
2
DI1
5
+5 V
6
GND
A
GENIbus A
Y
GENIbus Y
B
GENIbus B
3
GND
15
+24 V
8
+24 V
26
+5 V
23
GND
25
GDS TX
24
GDS RX
+5 V*
7
AI2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents