Trane AFDR Installation Instructions Manual page 62

Table of Contents

Advertisement

Installation
Table 17. Non-compressor specific parameters
ID
Description
0-03
Region Settings
0-20
Display Line 1.1 Small
0-24
Display Line 3 Large
0-40
[Hand on] Key on LCP
0-41
[Off] Key on LCP
0-60
Main Menu Password
0-61
Access to Main Menu w/o Password
1-03
Torque Characteristics
1-71
Start Delay
1-73
Flying Start
1-78
Compressor Start Max Speed [Hz]
1-79
Compressor Start Max Time to Trip
1-87
Trip Speed Low [Hz]
3-02
Min Reference
3-13
Reference Site
3-15
Reference 1 Source
3-41
Ramp 1 Ramp Up Time
3-42
Ramp 1 Ramp Down Time
4-10
Motor Speed Direction
4-12
Motor Speed Low Limit [Hz]
4-18
Current Limit
8-01
Control Site
8-03
Control Timeout Time
8-04
Control Timeout Function
8-30
Protocol
8-31
Address
8-82
Baud Rate
14-00
Switching Pattern
14-03
Overmodulation
14-10
Mains Failure
14-12
Function at Mains Imbalance
14-21
Automatic Restart Time
14-50
RFI Filter
14-51
DC Link Compensation
14-60
Function at Over Temperature
14-61
Function at Inverter Overload
14-62
Inv. Overload Derate Current
62
Values
[1] North American
[1612] Motor Voltage
[1617] Speed [RPM]
[0] Disabled
[0] Disabled
999
[1] LCP: Read Only
[0] Compressor Torque
2s
[0] Disabled
20Hz
10s
25Hz
30Hz
[1] Remote
[0] No Function
10s
10s
[0] Clockwise
30Hz
107%
[2] Controlword only
15s
[2] Stop
[2] Modbus RTU
3
[7] 115200 Baud
[1] SFAVM
[0] Off
[4] Kinetic Back-up
[3] Derate
8s
[0] Off
[1] On
[1] Derate
[1] Derate
75%
AFDR-SVN001D-EN