Solid State Starter Panel - Trane AFDR Installation Instructions Manual

Table of Contents

Advertisement

Solid State Starter Panel

Figure 35. Solid state starter component locations
1T2-1
1T2-2
1T2-3
1. Remove and discard high-fault bracing.
WARNING
Backup Wrench Required!
Failure to follow instructions below could result in
death or serious injury. Use backup wrench to prevent
twisting/stress on motor terminals when installing and
removing wire or buss bars from terminals and inspect
terminals to ensure that they are not damaged. Motor
terminals are ceramic and, if cracked, could create an
electrical hazard when power is restored.
2. Remove and discard power wire from breaker/
terminal, contactors, and motor terminals. See
Figure 33, p. 34
for use of backup wrench.
Note: Be sure to save motor terminal nuts for
installation.
3. Remove and discard 1F1/2/3 line side harness.
4. Remove relay 1K11.
5. Remove and discard current transformers: 1T2-1,
1T2-2, and 1T-31.
6. Remove and discard (if applicable) under/over voltage
transformers: T3-1, 1T3-2, and 1T3-1.
7. Remove and discard terminals 1X3.
AFDR-SVN001D-EN
Solid State
Starter
High Fault
Line-Side
Bracing
Harness 1F1/2/3
8. Remove and save Fuse 1F1/2/3 for later use.
Note: This fuse will be rated at 5 amps (380–415 volts)
9. Remove starter module 1A3.
Note: The liquid level red power wire (64A) is
10. Remove solid state starter module. See
p.
34.
1K11
1F1/2/3 Fuse
and 4 amps (460 volts).
connected to J3 Pin 1 of the starter module.
This will be connected to the power supply 1A2.
Refer to
"Panel Control Wiring," p.
Installation
1A3
1T3-1
1T3-2
1T3-3
48.
Figure 34,
35