Table 13. Pin-out, dual relay output (1A8)
Terminals—
1A8
Description
J11 Pins 1–4
PWR/Com
J2 Pin 6
Relay 115V in
J2 Pin 4
Relay N/O
AFD Control Wire Connections
8. Using 16 AWG wire make the following connections to
the AFD listed in
Table
Important:
Remove and discard white wire connecting Pin 12 and
Pin 37 on the AFD drive.
The red wire needs to be removed from the connector
on the UC800 end.
The red wire on the Modbus™ cable is NOT connected
to the AFD.
AFDR-SVN001D-EN
Mating
Connection
Description
LLID
WB2
communication/
power bus
1X5-4/7
To 115V "hot"
To Master Oil
1X5-2
Solenoid 4Y3 -
Wire: (29B)
14.
Table 14. Pin-out, AFD
Terminal—
AFD
Description
Modbus™
Pin 61
(RS485) Com
(BK)
Modbus™
Pin 68
(RS485) +
(BLU)
Modbus™
Pin 69
(RS485) – (GY)
Pin 4
Running Relay
Pin 5
Running Relay
Pin 37
Safe Stop
Pin 12
24V out
Figure 74. AFD—Remove white wire (safe stop)
Figure 75. AFD—Pin location safe stop and running
relay
Pins 4 and 5
(Running Relay2)
Pins 12
and 37
(Safe Stop)
Installation
Mating
Connection
Description
Modbus™
PIN 2 (IMC) UC800
(RS485) Com
1A1
(BK)
Modbus™
PIN 3 (IMC) UC800
(RS485) +
1A1
(BLU)
PIN 4 (IMC) UC800
Modbus™
1A1
(RS485) – (GY)
1X5-4/7
115V "hot"
1K15, pin A1
Coil – "hot"
1K14, pin 9
N/O contact
1K14, pin 5
N/O contact
Remove White Wire
From Pins 12 and 37
(Safe Stop)