A bell or visual indicator used as an arming acknowledgment signal must be listed to a ULC security, signaling
or fire standard. If intended to be mounted outside, it must be rated for outdoor use.
Fail secure locking mechanisms shall only be installed where allowed by the local authority having jurisdiction
(AHJ) and shall not impair the operation of panic hardware and emergency egress.
If fire resistance is required for door assembly, portal locking device(s) must be evaluated to ULC-S533 and
CAN/ULC-S104.
Must be installed with CAN/ULC-S319 listed portal locking device(s) for ULC installations.
If a flexible cord is used to connect to line voltage, strain relief must be provided for the cord inside the
enclosure or at the knockout.
The power supply is not intended to be mounted on the exterior of vault, safe, or stockroom.

CAN/ULC-S559

Signal Reporting
Any fault of an active communication system shall be annunciated and recorded at the signal receiving center
within 180 s of the occurrence of the fault.
The Report IP and Contact ID services must be programmed and enabled within the Protege system. The
following options are required:
-
The Contact ID Reporting Service must be enabled and the Service Mode must be configured to start
with the operating system.
-
Refer to the section
-
The Report IP Service must be enabled as the primary communication channel, the Service Mode must
be configured to start with the operating system, and the Reporting Protocol must be set to ArmorIP.
-
Refer to the section
-
The Trouble Area must be armed. Refer to the section
Operator Reference Manual.
In the ArmorIP Internet Monitoring Software the Poll Time must be set to 40 seconds and the Grace Time
must be set to 20 seconds. Refer to the section
Application User Manual.
Central Station Signal Receiver
The maximum number of signal transmitting units connected to any transmission channel shall conform to the
manufacturer's recommendations. The ArmorIP Receiver supports up to 10000 simultaneous connections.
Refer to the section
Internet Connections Requirements
details.
Number of attempts
In the event of unsuccessful communication, a digital alarm communicator transmitter shall make a minimum
of 5 and a maximum of 10 attempts. Where the maximum number of attempts to complete the sequence is
reached, an indication of the failure shall be made at the premises.
In the Protege system, the reporting service selected as Contact ID must have the number of attempts
programmed to 5 attempts. The Dialing Attempts option must be programmed. Refer to the section
ID | Settings
in the Operator Reference Manual.
If the PRT-4G-USB cellular modem is being used as the secondary reporting option in the installation, the
Report IP service assigned to the cellular modem must be programmed as above.
Check-In Time
DACT communication channel check-in time is not to exceed 24 hrs.
Trouble Input Service Test Report
-
The Test Report Time must be programmed. Refer to the section
Operator Reference Manual.
-
The Generate Input Restore on Test Input option must be enabled. Refer to the section
Options
in the Operator Reference Manual.
PRT-PX8-DIN | Protege DIN Rail 8 Output Expander | Installation Manual
Contact ID
in the Operator Reference Manual.
Report IP
in the Operator Reference Manual.
Poll/Grace Time
Trouble Inputs | Areas and Input Types
in the ArmorIP Version 3 Internet Monitoring
in the ArmorIP Receiver Installation Manual for further
Controllers | Configuration
in the
Contact
in the
Controller |
28