GEM eSyStep 639 S0 Series Operating Instructions Manual page 56

Positioner (code s0) motorized diaphragm valve
Table of Contents

Advertisement

12 Specific data IO-Link (pin 6)
12.4.29 Operating times
The current valve travel times can be read out with the Operating times parameter.
Index Sub-
Off-
Access
In-
set
Rights
dex
0x62
1
0
RO
2
8
RO
Description of parameter values
Index name
Operating times
12.4.30 Drive sets
The force of the actuator can be influenced with the Drive sets parameter when the valve is initialized and during initialization.
Index Sub-
Off-
Access
In-
set
Rights
dex
0x90
2
8
R/W
3
16
R/W
Description of parameter values
Index name
Drive sets
Force initialization
Force settings
Actuator size
AG0 and AG1
GEMÜ 639 eSyStep
Positioner (Code S0)
Length
Index name
8 bits
Operating times
8 bits
Parameter
Values
Open
0 to 255
0 to 25.5 s
Close
0 to 255
0 to 25.5 s
Length
Index name
3 bits
Drive sets
3 bits
Parameter
Values
Force
1 ... 6
1 ... 6
Setting parameter
Parameter
Type
Open
uint:8
Close
uint:8
Read out operating time (in tenths of seconds) from end pos-
ition CLOSED to end position OPEN.
Read out operating time (in tenths of seconds) from end pos-
ition OPEN to end position CLOSED.
Parameter
Type
Force
uint:16
Force initialization
uint:16
Set the force of the valve. Preset at the factory depending on
the valve type.
Set the force during initialization. Preset at the factory de-
pending on the valve type.
1
6
56 / 72
Default
Values
0
0 to 255,
0 to 25.5 s
0
0 to 255,
0 to 25.5 s
Description
Default
Values
-
1 ... 6
-
1 ... 6
Description
Force
Minimum force
Maximum force
www.gemu-group.com