Technical Data; Electrical Specifications - Eaton E DX Series Manual

Hide thumbs Also See for E DX Series:
Table of Contents

Advertisement

6 Technical Data

6.1 Electrical specifications:

1) For 1000H(XL)/ 2000H(XL)/ 3000H(XL):
INPUT
OUTPUT
2) For 6000H(XL)/10000H(XL):
Model
Power Rating
Frequency (Hz)
Voltage range
Voltage
Input
Current
Power Factor
Voltage
Current
Power Factor
Frequency tolerance
Output
Distortion
Overload capacity
Current crest ratio
Voltage
Battery
Current
Model No.
Phase
Frequency
Voltage
Current(A)
Voltage
Frequency
Wave form
Power rating
6000H
6KVA/4.2KW
30A max.
27A
Synchronized 46-54Hz in Utility mode (AC mode) 0.1% of normal
frequency in Battery mode
>130% load transfers to bypass mode after 1 second and shutdown the
240VDC
24A max
1000H(XL)
(46~54)Hz/(56~64)Hz
5A
1kVA/0.7kW
2kVA/1.4kW
6000HXL
6KVA/4.2KW
30A max.
>0.98 (Full load)
27A
THD<2% Full load (Linear Load)
105%-130% load transfers to bypass mode after 10 minutes
output after 1 minute
240VDC
24A max
17
2000H
2000HXL
Single
220~240V
10A
220/230/240V
50/60Hz
sinusoidal
2kVA/1.4kW
10000H
10KVA/7KW
50/60Hz
185~266V
220~240V
50A max
220~240V
46A
0.7
3:1 maximum
240VDC
40A max
3000H(XL)
16A
3kVA/2.1kW
10000HXL
10KVA/7KW
50A max.
46A
240VDC
40A max

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents