Eaton E Series DX User Manual

Eaton E Series DX User Manual

60-80kva (3-phase input/output)
Hide thumbs Also See for E Series DX:

Advertisement

Eaton E Series DX
60-80kVA
(3-phase input/output)
User Manual

Advertisement

Table of Contents
loading

Summary of Contents for Eaton E Series DX

  • Page 1 Eaton E Series DX 60-80kVA (3-phase input/output) User Manual...
  • Page 2 © 2011 Eaton Corporation ALL Rights Reserved The contents of this manual are the copyright of the publisher and may not be reproduced(even extracts)unless permission granted. Every care has been taken to ensure the accuracy of the information contained in the manual,but no liability can be accepted for any errors...
  • Page 3 UPS internal circuitry or batteries. 2. When applied to the following types of equipment, please contact the distributor or Eaton prior to installation, as there may be special design, application and maintenance requirements: A.
  • Page 4 3. If the UPS is relocated or re-wring is necessary, AC input power and battery should be switched off and UPS should be completely turned off to avoid risk of electric shock. 4. Please use Eaton specified accessories. Battery Safety 1. Battery service lifetime will be shortened as ambient temperature rises. Replace batteries periodically to guarantee normal UPS performance and sufficient back- up time.
  • Page 5 Maintenance 1. Storage and operating environment can affect the service life and reliability of this product. The product is not suitable for performance in the following environment: A. Locations where temperature or humidity exceeds the maximum or goes below the minimum levels as shown in the technical specifications (temperature range: 0-40℃...
  • Page 6: Table Of Contents

    C o n t e n t s C h a p t e r 1 B r i e f i n t r o d u c t i o n ..............1 1.1 Product introduction ....................1 1.2 Frequently used symbols ...................2 C h a p t e r 2 E x t e r i o r a p p e a r a n c e ...............3 2.1 Unpacking inspection....................3 2.2 Exterior figure......................5...
  • Page 7: Chapter 1 B R I E F I N T R O D U C T I O N

    Chap t e r 1 B r i e f i n t r o d u c ti o n 1.1 Product introduction EDX Series products are high-efficiency and high-performance, double conversion, true online three phase input and three phase output UPS. This series provides protection from disturbances and problems such as outages, surges, brownouts, sags, harmonic distortion, and frequency fluctuation and can be widely used to protect computer equipment, communications equipment and...
  • Page 8: Frequently Used Symbols

    1.2 Frequently used symbols The following symbols will be frequently used in this User Manual as well as in the process of actual application.
  • Page 9: Chapter 2 E X T E R I O R A P P E A R A N C E

    Chap t e r 2 Ex t e r i o r a p p e a r a n c e 2.1 Unpacking inspection 1. The UPS packing case should contain the following: 1) UPS. 2) Accessories including user manual, Winpower Disc and two door keys. 2.
  • Page 10 Note:For EDX 60KVA/80KVA models, remove the steel brackets fixing the UPS to the pallet. Then move the frame smoothly from the pallet to the ground. If required, the UPS can be fixed to the floor by re-using the packaging steel brackets.
  • Page 11: Exterior Figure

    2.2 Exterior figure LCD panel Button LED indicator light Front view Front view(without front panel) top view bottom view 2.3 Panel instructions The LCD panel is the interface used to operate the UPS. It consists of three parts: LED indicators, LCD and function keys.
  • Page 12 Note: Please refer to Appendix 2 for detailed information on LED indication of the UPS status. Status LED Indicator: Display the current UPS operating mode or status. Identifier LED Indicator Color Status green UPS is powered directly by AC ① Inverter green UPS is powering through the inverter...
  • Page 13: Chapter 3 I N S T A L L A T I O N I N S T R U C T I O N S

    Chapt e r 3 I n s t a ll a t i o n in s t r u c t i o n s 3.1 Installation Notice 1) The installation of EDX series products must be performed in compliance with the relevant electrical codes by qualified personnel.
  • Page 14: Installation And Wiring Connection Diagram

    3.3 Installation and wiring connection diagram EDX 60KVA/80KVA standard models feature single power input. The UPS can be converted from single power source to dual power source by Eaton customer service engineers on site. All operations should only be carried out by trained service personnel authorised by Eaton.
  • Page 15 single power input(3Φ4W):60kVA~80kVA connection diagram Notes: Please make sure that the input power is three-phase with 4 wires, and the input voltage is within the allowable voltage range (refer to Appendix 1). Make sure the input power phase sequence is clock-wise and battery polarities are correctly connected.
  • Page 16: Requirements Of Wiring Cables And Protect Device For Edx Series Ups

    3.4 Requirements of wiring cables and protect device for EDX series External batteries of EDX Series UPS require serial connection of positive and negative for each group of 14-16 batteries (12VDC per battery) with the same capacity, nominal voltage for each group being 168VDC-192VDC. Battery capacity and number of groups can be selected at your option.
  • Page 17: Parallel Ups Installation

    3.5 Parallel UPS installation 1. Redundancy introduction N+X is currently the most reliable power supply structure, in which N indicates the minimum UPS number required for the total load and X is the redundant UPS number, namely, the malfunctioning UPS number that the system can simultaneously bear.
  • Page 18: Procedures Of Connecting Battery Bank To Ups

    3.Parallel machine wire connection drawing: 3.6 Procedures of connecting battery bank to UPS The rated over-current protection breaker should be installed between the battery bank and the UPS, please refer to the wiring table at the last section for the specification.
  • Page 19 Remark: Battery connection and replacement should be operated with the system shutdown, by qualified personnel.
  • Page 20: Chapter 4 O P E R A T I O N

    C ha pte r 4 O p e r a t i o n 4.1 Single UPS operation 1. Make sure L1, L2 and L3 phase sequences are correctly connected and then supply power to UPS. 2. Turn on the battery circuit breaker in the battery cabinet (make sure that the “+”, “N”...
  • Page 21 3) Press ESC to access information 4) Press▼to obtain the below information (will automatically display after 1min) 5) Press▼again to obtain the below 6) Press▼again to obtain the below information information 7) Press▼again to obtain the below 8) Press▼again to obtain the below information information...
  • Page 22 9) Press▼again to obtain the below 10) Press▼again to obtain the below information information Remark: when malfunction occurs, “ ” will appear at the lower right corner of the picture while when warning occurs “ ” will appear at the same position (as illustrated in the below picture with battery mode as an example).
  • Page 23 3) Select “Yes, Confirm” to switch on 4) Normal Switch-on the machine 5) Battery power supply (switch off line input breaker) 5. Switch-off action (press ESC to exit above picture)
  • Page 24 1) Switch-off picture 2) If it is in single machine mode, the following will appear 3) If it is in parallel machine mode, the 4) Press ENTER following will appear 5) Select “Yes, Confirm” to switch off the machine...
  • Page 25 Remark: If you intend to switch off only one set of UPS within a multi-module parallel system, select “single machine switch-off”; if switch-off is intended for the entire multi-module parallel system, select “parallel machine switch-off”. 6. Help 1) Help picture 2) Press ENTER on help picture 3) Press ENTER on SERVICE HOTLINE picture...
  • Page 26 7. Setting action (press ESC to exit the above picture) You are able to access Setting picture by using user combination (default: 1234, subject to personal modification) so as to set the following programs. 1) Setting picture (bypass power supply) 2) Press▼...
  • Page 27: Parallel Ups Operation

    8. EDX Series is capable of DC start-up without AC input, panel display being similar to switch-on picture with AC supply. DC switch-on and off are available by following instructions appearing in the pictures: Firstly, activate DC switch-on function set under the bypass mode; Make sure that “+”, “-”...
  • Page 28 3) Select to switch off one of the single machines or the parallel system: Remark: After turning on in Line mode, all UPSs will transfer to INV mode; Turn off: when turn-off is conducted under INV mode, all UPSs will simultaneously turn off inverter and then transfer to the bypass mode, if the UPSs are turned off one by one, all UPSs will simultaneously transfer to the bypass mode after the last UPS completes turn-off action.
  • Page 29: Chapter 5 C O M M U N I C A T I O N I N T E R F A C E

    External Battery Temperature Probe connection port, AS400 relay port, EPO, RS485 and RS232 ports as well as Service Supervising Communication Interface exclusively available to Eaton technical personnel. EDX 60KVA/80KVA 1. Intelligent slot: suitable for WebPower card (optional), enabling you to realise remote supervisory management of UPS by accessing Internet.
  • Page 30 7. SERVICE Interface: available only to Eaton service personnel and not open to users. 8. Standard RS232 Interface: applicable to WinPower management software (See Appendix for RS232 port Pin definition). AS400 PORT: Pin# Description UPS Fail Output Summary Alarm Output...
  • Page 31 RS485 PORT: Pin# Description RXDA Input RXDB Input TXDB Output TXDA Output RS232 PORT: Pin# Description Output Intput Output...
  • Page 32: C Hap T Er 6 O Pt Io N A L A C C E S S Or I Es

    C hap t er 6 O pt io n a l a c c e s s or i es 6.1 Transformer For loads that are sensitive to common mode voltages (Neutral to Earth) the installation of a special transformer to the output will reduce the Neutral-to Ground voltage to less than 1V.
  • Page 33 IP21 Option...
  • Page 34: Chapter 7 Transportation, Maintenance And Troubleshooting

    Chapter 7 Transportation, Maintenance and Troubleshooting Move the UPS Make preparation for UPS relocation according to the following steps. Remark: special equipment (fork-lift) is needed for loading and unloading due to the heavy weight of the UPS. 1. Switch off all equipments connected to UPS. 2.
  • Page 35 Press ESC for more than LCD panel has no 3 secs, or replace LCD if display faulty If problems still exist, please contact EATON service and provide the following information: MODEL and SERIAL NO of the UPS: 110224-85870001 Failure date Detailed failure description (including LCD malfunction, indicator condition, buzzer information, power and load capacity etc.).
  • Page 36: Appe N D I X 1 Te Ch Ni Cal Par Amet E Rs And S Pe Cif Icatio Ns

    A ppe n d ix 1 Te ch ni c a l p ar am et er s an d s p e c i f ic a tio ns Model EDX 60KVA EDX 80KVA Power Rating 60KVA/48KW 80KVA/64KW Connection 3-Phase + N+G Frequency 40-70Hz...
  • Page 37: A Ppe N Dix 2 D Is Pl Ay R E F E R E N C E T A B Le

    A ppe n dix 2 D is pl ay r e f e r e n c e t a b le Indicator Working condition Buzzer Bypass Line Inverter Battery Fault LED Standby Mode One flash One beep Normal    ...
  • Page 38   every 4 sec every 4 sec Should any display or warning message excluded in the above table be found, please contact your distributor or call Eaton service for advice. ● Indicator light is on ★ Indicator light flashes Warning include one or more than one of these: 1.EPO active...
  • Page 39 614-03807-01...

This manual is also suitable for:

Edx 60kvaEdx 80kva

Table of Contents