1.4 Technical data

Model
Dimensions
(W x D x H) (mm)
Net Weight (Kg)
Power Rating
Apparent power (KVA)/
Active power (KW)
Input
Voltage range
Current*
Frequency range
Power factor
Output
Voltage*
Stability
Frequency
Power factor
Overload capacity
Distortion
Battery (the battery life reduce quickly under high temperature)
Backup time
Charge time
EMC
EMI
EMS
Caution: This product for commercial and industrial application in the second
environment installation restrictions or additional measures may be needed to prevent
disturbances.
Operation temperature
Storage temperature
Humidity
Altitude
C-6000FC
111
220(adjustable according to customer requirements)
56Hz~64Hz (line mode, synchronize with line)
105%~125%: transfer to bypass after 1 min;
125%~135%: transfer to bypass after 30 seconds;
>135%: transfer to bypass after 0.1 second;
> 7 mins
(4200W)
7 hours to 90%
CNS 14757-2(C3)
ESD
IEC61000-4-2 Level 4
RS
IEC61000-4-3 Level 3
EFT
IEC61000-4-4 Level 4
Surge
IEC61000-4-5 Level 4
0°C~40°C
-25°C~55°C
20%~90% (no condensation)
<1000m
C-6000FCL
C-6000F
577× 290× 755
59
6KVA/
4.8KW
220VAC (-15%/+25%)
33A.max
60Hz(+/-4Hz)
0.99
±1%
60Hz±0.05 (battery mode)
0.8
THD<2% (full linear load)
> 5 mins
(4200W)
7 hours to 90%
4
C-6000FL
99
59

Hide quick links: