Delta DVP02DA-S Instruction Sheet page 5

Analog output module
Hide thumbs Also See for DVP02DA-S:

Advertisement

Available languages

Available languages

RS-485
CR
parameters
Latched
#
address
#32
H'4052
○ R/W Communication format setting
#33
H'4053
○ R/W
CR#33 is used to set the internal function priority. For example: characteristic register. Output latched function will save
output setting to the internal memory before power loss.
#34
H'4054
R
#35 ~ #48
Symbols: ○ means latched. (Only valid when written in via RS-485 communication)
╳ means not latched.
R means can read data by using FROM instruction via RS-485.
W means can write data by using TO instruction via RS-485.
LSB (Least Significant Bit): 1. Voltage output: 1
※ Added the RESET function for modules with firmware V4.06 or later. Connect the module power input to 24 VDC and
write H'4352 into CR#0 and then turn the power off and on again; all parameters in modules, including communication
parameters are restored to factory defaults.
※ The corresponding parameters address H'4032 ~ H'4054 of CR#0 ~ CR#34 are provided for users to read/ write data
via RS-485 communication.
※ If you want to use Modbus address in decimal format, you can transfer a hexadecimal register to decimal format and
then add one to have it become a decimal Modbus register address. For example transferring the address "H'4032" of
CR#0 in hexadecimal format to decimal format, to have the result 16434 and then adding one to it, you have 16435, the
Modbus address in decimal format.
※ Function codes: 03'H is for reading data from registers. 06'H is for writing a word data into registers. 10'H is for writing
multiple word data into registers.
※ CR#32 communication format settings: for modules with firmware V4.04 or previous versions, b11~b8 data format
selection is not available. For ASCII mode, the format is fixed to 7, E, 1 (H'00XX) and for RTU mode, the format is fixed
to 8, E, 1 (H'C0xx/H'80xx). For modules with firmware V4.05 or later, refer to the following table for setups. Note that
the original code H'C0XX/H'80XX will be seen as RTU, 8, E, 1 for modules with firmware V4.05 or later.
b15 ~ b12
ASCII/RTU,
exchange low and high byte of CRC
check code
Register name
Reset to default setting and
set characteristics adjustable
priority
Software version.
System used
=10V/8,000=2.5mV.
LSB
2. Current output: 1
=20mA/4,000=5μA.
LSB
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
It is used to set communication format.
For baud rate, the settings are
4,800/9,600/19,200/38,400/57,600/115,200 bps.
Communication format:
ASCII:7,E,1 / 7,O,1 / 8,E,1 / 8,O,1 / 8,N,1
RTU :8,E,1 / 8,O,1 / 8,N,1
Factory default : ASCII,9600,7,E,1 (CR#32=H'0002)
Refer to ※CR#32 communication format settings at the end
of this table for more information.
Reserved
Output latched setting, default setting H'0000.
Give CH1 setting for example:
1. When b0=0, user can set OFFSET and GAIN value of CH1
(CR#22, CR#28). When b1=1, inhibit user to adjust
OFFSET and GAIN value of CH1 (CR#22, CR#28).
2. The value of b1 determines whether a characteristic
register is latched while using RS485 to read-write control
registers. b1=0 (latched), b1=1 (not latched).
3. When b2 is set to 1, all settings will be reset to default
setting.
In hexadecimal to display software version.
For example: H'010A means 1.0A.
b11 ~ b8
Data format
Description
CH2
CH1
b7 ~ b0
Baud rate