 Other Specifications
Max. rated power
consumption
Operation/storage
Vibration/shock immunity
 CR (Control Register)
RS-485
CR
parameters
Latched
#
address
#0
H'4032
R
#1
H'4033
○ R/W Output mode setting
CR#1: CR#1 is used to set two internal channels working mode of analog output module. Every channel has four modes
to set that can set individually. For example: if set CH1 to mode 2 (b2 ~ b0 = 010), CH2 to mode 1 (b5 ~ b3 = 001). It
needs to set CR#1 to H'000A.
#10
H'403C
╳ R/W CH1 output value
#11
H'403D
╳ R/W CH2 output value
#22
H'4048
○ R/W
#23
H'4049
○ R/W
#28
H'404E
○ R/W To adjust GAIN value of CH1
#29
H'404F
○ R/W To adjust GAIN value of CH2
CR#22~CR#29: Please be noticed that GAIN value – OFFSET value=+400
value within this range, the resolution of the output signal will be thin and the value variation will be larger. When this value
exceeds this range, the resolution of output signal will be thick and the variation of value will be smaller.
#30
H'4050
R
CR#30 is the error code. Please refer to the following chart.
Error description
Power source abnormal
Analog input value error
Setting mode error
Offset/gain error
Digital range error
Average times setting error
Instruction error
Note: Each error code will have corresponding bit (b0 ~ b7). Two or more errors may happen at the same time. 0 means normal
and 1 means error happened.
EX: if the digital input exceeds 4,000, error (K2) will occur. If the analog output exceeds 10V, both analog input value
error K2 and K32 will occur.
#31
H'4051
○ R/W
24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%), 3W, supply from external power.
1. Operation: 0°C~ 55°C (temperature), 5 ~ 95% (humidity), pollution degree 2
2. Storage: -25°C~ 70°C (temperature), 5 ~ 95% (humidity)
Standard: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST Ea)
Register name
Model type
To adjust OFFSET value of
CH1
To adjust OFFSET value of
CH2
Error status
Content
K1 (H'1)
K2 (H'2)
K4 (H'4)
K8 (H'8)
Reserved
K32 (H'20)
K64 (H'40)
K128 (H'80)
Communication address
setting
Power supply
Environment
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
System used, data length is 8 bits (b7 ~ b0).
DVP-04AD model code=H'49.
User can read the data from program to check if there is
extension module.
Output mode setting: default setting is H'0000.
Mode 0: output voltage mode (0V ~ 10V).
Mode 1: output voltage mode (2V ~ 10V).
Mode 2: output current mode (4mA ~ 20mA).
Mode 3: output current mode (0mA ~ 20mA).
Mode 4: none use.
The output setting range of channel CH1 ~ CH2 is K0 ~
K4,000. Default setting is K0 and unit is LSB.
It is used to set the OFFSET value of CH1 ~ CH2.
The setting range is K-2,000 ~ K2,000.
The default setting is K0 and unit is LSB.
It is used to set the GAIN value of CH ~ CH2.
The setting range is K0 ~ K4,000.
The default setting is K2,000 and unit is LSB.
It is the data register to save all error status.
Please refer to error code chart for detail.
b15 ~ b8
b7
b6
0
0
0
0
0
0
0
0
0
0
0
1
1
0
It is used to set RS-485 communication address. The setting
range is from 1 to 254 and the default setting is K1.
Reserved
~+6,000
(voltage or current). When this
LSB
LSB
b5
b4
b3
0
0
0
0
0
0
0
0
0
0
0
1
1
0
0
0
0
0
0
0
0
CH2
CH1
b2
b1
b0
0
0
1
0
1
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0