5 System and product information
• Can be mounted simply in the shaft with mount-
ing support or the mounting grooves. Accessor-
ies for mounting support UPM 60/100 or mount-
ing grooves ER-MS (installation kit: 4 hammer
head screws, nuts and 90° brackets).
• Can be screwed directly into the front wall or
ceiling (4 slots in the external frame).
• Mains cable type NYM-O or NYM-J, 3 x 1.5 or 5
x 1.5 mm², depending on the cover variant.
Fan insert
• Fan insert for installation in housing.
• Electrical plug connection for quick installation
in the housing.
• Energy-saving EC motor.

5.5 Covers: Functions

Filter change indicator
(6 months) with TimeStrip
Filter change indicator
(6 months) with LED
Control with time module
Control with fully automatic humidity control: Extraction
takes place automatically if the specified switch-on hu-
midity is exceeded.
Control with motion detector. Full load level after motion
is detected (range motion sensor is 5 m)
Barrier-free product, as it switches itself on and off auto-
matically
Not speed controllable
Electrical plug connection for quick connection of the ER
EC with ER GH housing and ER-AK, ER-AH or ER-AB
with the ER EC fan insert.
Air volume – base load 30 m³/h for continuous operation
Air volume of the base load and full load levels can be set
Additional air volumes that can be set
in base load: 20 m³/h, 40 m³/h, 60 m³/h or 100 m³/h and
in full load: 20 m³/h, 30 m³/h, 40 m³/h or 100 m³/h
Full load level on/off via light switch or separate switch.
During manual operation (e.g. using light switch), the
start delay and overrun time apply.
Full load operation (60 m³/h) with start delay of 60
seconds and overrun time of 15 minutes, non-adjustable
Full load operation (60 m³/h), start delay can be set with
0, 30, 60*, 90 or 120 seconds
Overrun time of the full load level can be set for 0, 3, 6,
15*, 24 or 30 minutes
• Motor not speed controllable.
• Air outlet adapter (scope of delivery) for conver-
sion of air outlet towards the rear.
Covers
• Cover with exhaust air filter. Trouble-free filter
change without tools.
• ER-AH and ER-AB: Barrier-free products,
switch on and off automatically.
• ER EC fans with water jet protection for areas 1
(DIN VDE 0100-701).
• It is possible to rotate the cover by ± 5° to com-
pensate for housings which have been fitted at
an angle.
ER-A
ER-AK
ER-AH