8-2-3.Monitor Function Of Remote Controller Switch - Toshiba RAV-GP561ATW-E Service Manual

Air-conditioner split type
Hide thumbs Also See for RAV-GP561ATW-E:
Table of Contents

Advertisement

8-2-3. Monitor Function of Remote Controller Switch
Calling of sensor temperature display
<Contents>
Each data of the remote controller, indoor unit and outdoor unit can be understood by calling the service monitor
mode from the remote controller.
<Procedure>
1
Push
+
buttons simultaneously for 4 seconds to call
the service monitor mode.
The service monitor goes on, the header indoor unit No. is displayed
at first and then the temperature of CODE No.
2
Push temperature set
CODE No. of data to be monitored.
The CODE No. list is shown below.
CODE No.
01
Room temperature (Remote controller)
02
Indoor room air temperature (TA)
03
Indoor heat exchanger (Coil) temperature
(TCJ)
04
Indoor heat exchanger (Coil) temperature
(TC)
07
Indoor fan revolution frequency
F2
Indoor fan calculated operation time
F3
Indoor unit fan cumulative operating
hours
F8
Indoor discharge temperature
3
UNIT LOUVER
Push
button to select the indoor unit to be monitored.
Each data of the indoor unit and its outdoor units can be monitored.
4
Pushing
button returns the status to the usual display.
The indoor discharge temperature of CODE No. [F8] is the estimated value from TC or TCJ sensor.
Use this value to check discharge temperature at test run.
(A discharge temperature sensor is not provided to this model.)
• The data value of each item is not the real time, but value delayed by a few seconds to ten-odd seconds.
buttons and then change the
Data name
Unit
rpm
×100h
×1h
is displayed.
CODE No.
°C
60
Outdoor heat exchanger (Coil)
°C
temperature (TE)
°C
61
Outside temperature (TO)
62
Compressor discharge temperature (TD)
°C
63
Compressor suction temperature (TS)
65
Heat sink temperature (THS)
6A
Operation current (×1/10)
6D
Outdoor heat exchanger (Coil)
temperature (TL)
70
Compressor operation frequency
°C
72
Outdoor fan revolution frequency (Lower)
73
Outdoor fan revolution frequency (Upper)
F1
Compressor calculated operation time
66
TEMP.
TIMER SET
FAN
TIME
SAVE
A
FILTER
L
RESET
TEST
SET
CL
SWING/FIX
2
4
1
<Operation procedure>
1
2
3
Returned to usual display
Data name
ON / OFF
MODE
VENT
UNIT LOUVER
3
4
Unit
°C
°C
°C
°C
°C
A
°C
rps
rpm
rpm
×100h

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-gp801atw-eRav-gp561atw-trRav-gp801atw-tr

Table of Contents