Failure mode detected by remote controller or central controller (TCC-LINK)
Operation of diagnostic function
Check code
Cause of operation
No communication with header indoor
unit
• Remote controller wiring is not
Not displayed
correct.
at all
• Power of indoor unit is not turned
(Operation on
remote
on.
controller is
• Automatic address cannot be
impossible.)
completed.
No communication with header indoor
unit
• Disconnection of inter-unit wire
E01
between remote controller and
*1
header indoor unit
(Detected by remote controller side)
Signal send trouble to indoor unit
(Detected by remote controller side)
E02
There are multiple master remote
controllers.
E09
(Detected by remote controller side)
L20
Duplicated indoor central addresses
on communication of central control
Central
system
controller
(Detected by indoor / central
L20
controller side)
Communication circuit trouble of
*2
central controller
(Detected by central controller side)
Central
controller
(Send)
C05
(Receive)
C06
Indoor Gr sub unit trouble
(Detected by central controller side)
Central
controller
P30
*1 The check code cannot be displayed by the wired remote controller.
(Usual operation of air conditioner becomes unavailable.)
For the wireless models, a trouble is notified with indication lamp.
*2 This trouble is related to communication of remote controller (A, B), central system (TCC-LINK U3, U4), and [E01], [E02], [E03], [E09] or
[E18] is displayed or no check display on the remote controller according to the contents.
Status of air
Condition
conditioner
Stop
Stop
(Automatic
reset)
Displayed
* If central
when trouble is
controller
detected
exists,
operation
continues.
Stop
(Automatic
reset)
Displayed
* If central
when trouble is
controller
detected
exists,
operation
continues.
Stop
Displayed
(Follower unit
when trouble is
continues
detected
operation.)
Stop
Displayed
(Automatic
when trouble is
reset)
detected
Continues
Displayed
(By remote
when trouble is
controller)
detected
Continuation /
Displayed
Stop
when trouble is
(According to
detected
each case)
72
Judgment and measures
Power supply trouble of remote controller, Indoor
EEPROM trouble
1.Check remote controller inter-unit wiring.
2.Check remote controller.
3.Check indoor power wiring.
4.Check indoor P.C. board.
5.Check indoor EEPROM.
(including socket insertion)
→ Automatic address repeating phenomenon
generates.
Receiving trouble from remote controller
1.Check remote controller inter-unit wiring.
2.Check remote controller.
3.Check indoor power wiring.
4.Check indoor P.C. board.
Sending trouble of remote controller
1.Check sending circuit inside of remote controller.
→ Replace remote controller.
1.In 2-remote controllers (including wireless), there
are multiple header units.
Check that there are 1 master remote controller
and other sub remote controllers.
1.Check setting of central control system network
address. ("1 : 1 Model" Connection Interface
SW01)
2.Check "1 : 1 Model" Connection Interface P.C.
board.
1.Check communication wire / miswiring
2.Check communication (U3, U4 terminals)
3.Check "1 : 1 Model" Connection Interface P.C.
board.
4.Check central controller (such as central control
remote controller, etc.)
5.Check terminal resistance. (TCC-LINK)
Check the check code of the corresponding unit from
remote controller.
"1 : 1 Model" Connection Interface: TCB-PCNT30TLE2