(3) Outdoor fan revolution number control
Control of fan revolution number and the fan taps in this unit are shown below.
W1
W2
GP56
240
320
GP80
200
200
(3)-1. Cooling fan control
(1) Cooling operations of the outdoor fan are controlled by a TL sensor, TO sensor and the compressor
revolution number.
The outdoor fan is controlled by every 1 tap of DC fan control (15 taps).
During startup, operation is fixed for 60 seconds by a maximum fan tap corresponding to the zones
shown in the table below. Thereafter fan tap is controlled by a temperature outputted from the TL sensor.
20 rps or lower
GP56
Min.
38°C ≤ TO
W6
29°C ≤ TO < 38°C
W5
15°C ≤ TO < 29°C
W4
5°C ≤ TO < 15°C
W3
0°C ≤ TO < 5°C
W2
-4°C ≤ TO < 0°C
W2
TO < -4°C
OFF
TO trouble
OFF
20 rps or lower
GP80
Min.
38°C ≤ TO
W6
29°C ≤ TO < 38°C
W5
15°C ≤ TO < 29°C
W3
5°C ≤ TO < 15°C
W2
0°C ≤ TO < 5°C
W1
-5°C ≤ TO < 0°C
W1
TO < -5°C
OFF
TO trouble
OFF
Fan Taps Revolution number Allocation [rpm]
W3
W4
W5
W6
320
390
400
470
200
230
260
290
20 rps to 45 rps
Max.
Min.
WC
W8
WB
W7
W8
W6
W6
W5
W4
W4
W3
W3
OFF
OFF
WC
OFF
20 rps to 52 rps
Max.
Min.
WB
W8
WA
W7
W7
W5
W5
W4
W3
W3
W2
W2
OFF
OFF
WB
OFF
W7
W8
W9
510
550
560
330
360
410
45 rps or higher
Max.
Min.
Max.
WF
WA
WF
WD
W9
WD
WA
W8
WC
W8
W7
WA
W6
W5
W8
W5
W4
W6
W1
OFF
W1
WF
OFF
WF
52 rps or higher
Max.
Min.
Max.
WE
WA
WE
WD
W9
WD
W9
W7
WB
W7
W6
W9
W5
W4
W7
W4
W3
W5
W2
OFF
W3
WE
OFF
WE
56
WA
WB
WC
WD
570
570
650
700
450
480
500
540
TL [˚C]
WF tap
56
55
+1 tap / 20 sec.
Up to the maximum
revolution frequency of each zone
38
Revolution frequency hold
35
–1 tap / 20 sec.
Down to the minimum
revolution frequency of each zone
TL [˚C]
58
55
+1 tap / 20 sec.
37
Revolution number HOLD
34
WE
WF
750
830
570
600
WF tap