7-7-11. Monitor Function of Remote Controller Switch

Switching to the service monitor mode
<Content>
The sensor temperature or operation status of the remote controller, indoor unit, or the outdoor unit can be
known by switching to the service monitor mode from the remote controller.
[Procedure]
<RBC-AMT*>
1
Push
+
buttons simultaneously for 4 seconds or more
to call up the service monitor mode.
The service monitor goes on, and temperature of the CODE No. 00 is
firstly displayed.
2
Push the temperature setup
CODE No. to be monitored.
For displayed codes, refer to the table next page.
3
Push
button to determine the item to be monitored.
Then monitor the sensor temperature or operation status of indoor unit
and the outdoor unit in the corresponding refrigerant line.
4
Pushing
button returns the display to the normal display.
<RBC-AWSU**>
00
buttons to select the
0024
- 164 -
2
FILTER
RESET
1
Push the [
Menu] button to display the
menu screen
2
Push and hold the [
the [
] button at the same time to
display the "Field setting menu".
→Push and hold the buttons for more than 4
seconds
3
Push the [
] / [
"4.Monitor function" on the "Field setting
menu" screen, then push the
"
Set" [
Set / Fix] button.
Push the [
the code to check data.
4
Refer to the installation Manual supplied
with the indoor unit or outdoor unit or
service manual for details about the check
5
Push the "
Return" [
button to return to
the "Field setting menu" screen.
TEMP.
ON / OFF
TIMER SET
FAN
MODE
TIME
SAVE
VENT
TEST
SET
CL
SWING/FIX
UNIT LOUVER
4
3
1
Menu] button and
] button to select
] / [
] button to select
Return]