Interlock - Nuvation Energy High-Voltage BMS Installation Manual

Table of Contents

Advertisement

5.3.2. Interlock

The Interlock connector provides a means to set the high-current contactor behavior, as outlined in
the table below. Using a physical switch/relay instead of a jumper is a convenient way to implement
an interlock switch that de-energizes the system contactors. It is recommended to connect pins 2 and
3 as this will enable the hardware redundant fault signaling feature to de-energize system contactors
in the event of a Power Interface failure.
Interlock Connection
1 & 3
open
open
closed
Pin 3 is electrically connected to chassis ground
Connect a jumper or external interlock switch to this connector.
Document ID: NE-IG-001
Table 25. Interlock Options
2 & 3
open
closed
either open or closed
Table 26. Interlock: Molex Micro-Fit Connector
Molex 43645-0300
Manufacturer
Housing
Housing material
Circuits
Crimp terminal
Wire gauge range
Nuvation Energy High-Voltage BMS - Installation Guide
Function
System contactors are de-energized
System contactors are controlled by Nuvation Energy
BMS software, but de-energized if hardware-based
fault signaling detects a fault
System contactors are controlled by Nuvation Energy
BMS software; hardware-based fault signaling
mechanism will not de-energize system contactors
Molex Incorporated
43645-0300
Nylon UL94V-0
3
43030-0002
AWG20-24 stranded
31
Rev 2.1, 2020-03-13