Panel Terminal Connections, Jumper Placements, and DIP Switch
Settings

Reference Aids

Procedure

Refer to the 841-921 Field Wiring Diagram, the information sheets mounted on
the inside of the 4003 panel door, and the procedure listed below when installing
the 4003 VCP.
Follow the steps listed below when installing the 4003 VCP.
1.
Connect ground wire from electrical distribution panel to the 4003 green
grounding screw.
2.
Connect external speakers circuit to TB1-1 (SIG +) and TB1-2 (SIG -) on
the 4003 SIGcard.
3.
Install jumper in position 1-2 of P3 on the 4003 SIGcard.
4.
Install and connect additional SIGcard as required.
5.
Set the Voice Controller Assembly DIP Switch SW3 as required.
6.
If 4003 is being used in Adjunct Mode, select desired message using Voice
Controller Assembly DIP Switch SW2 and jumper P3.
7.
Verify jumper settings on the 562-907 Amplifier Board Assembly.
Install J1, J3, J5, J7, J11, and J15.
Remove R4, R10, R38, C5, and JW1.
8.
If 4003 is being used in 4020 Slave Mode, select RUI COMMS using
Voice Controller Assembly DIP Switch SW6.
Set SW6-1 and SW6-2 ON.
Set SW6-3 and SW6-4 OFF.
9.
If 4003 is being used with a 4100 or 4020, track NAC by installing jumper
to position 2-3 of P2, all other panels install jumper to position 1-2 of P2.
For Voice Message or non-coded operation, install jumper to position 1-2 of
P2 and position 2-3 of P9 on Voice Controller Assembly. For coded horn
operation install jumper to position 2-3 of P2 and 1-2 of P9. To select
Temporal Code install jumper to position 2-3 of P3.
31
firealarmresources.com
Continued on next page