Bryant 619AHB Series Service Manual page 18

High wall ductless system sizes 06 to 36
Hide thumbs Also See for 619AHB Series:
Table of Contents

Advertisement

SG-619AHB-01: Service Manual
DIAGNOSIS AND SOLUTION (CONT)
Indoor / outdoor unit's communication diagnosis and solution (E1)
Malfunction Decision Conditions
Indoor unit does not receive feedback from the outdoor unit for 110 seconds and this condition happens four times continuously.
Possible Causes:
• Wiring error
• Indoor or outdoor PCB faulty
Troubleshooting
Replace the reactor.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Power off, then restart the unit 2 minutes later.
Yes
Measure Vs. Is it a positive fluctuation?
(Vs represents the voltage S and N of the
outdoor unit. Red pan-S, Black pan-N)
Yes
Check the outdoor wiring connection.
Yes
Yes
Check whether the
No
reactor is normal.
Yes
Replace the outdoor main PCB.
Power on. Is the error resolved?
No
Replace the indoor main PCB.
Check the indoor wiring connection.
Replace the indoor main PCB.
Power on. Is the error resolved?
Replace the outdoor main PCB.
18