BATTERY REPLACEMENT PROCEDURE:
1.
Disconnect the UPS from the power source and slide the battery door open.
See pictures 1 and 2.
2.Disconnect the battery and remove as indicated below. See pictures 3 and 4
3.Insert the replacement battery and reconnect the battery cables.
See pictures 6 and 7
NOTE:
It is important that the connectors be firmly attached to new batteries.
4.Reposition the battery door and slide closed. See pictures 8 and 9.
NOTE: Properly recycle used battery.
4.5AH, 5AH batteries (350VA, 500VA models)
7AH x 1 battery (700VA models)
7AH x 2, 9AH x 2 batteries (1000VA, 1500VA models)
STATUS INDICATORS
The UPS provides both visual and audible status indicators. Visual indicators
consist of three LEDs to represent the following conditions:
On utility power operation
On battery power operation
UPS fault/alarm
LED Indicator Table
On Utility (AC mode)
Green Lighting
On Battery (Backup mode)
Yellow Lighting
Low Battery
Yellow Flashing
Fault/Output Short
Red Lighting
Overload/Check Battery
Red Flashing
LED Audible Alarm Table
Backup mode
Sounding every 5 seconds
Battery low
Sounding (two beeps) every 5 seconds
Overload
Sounding every 0.5 seconds
Replace battery
Sounding (three beeps) every 30 seconds
Fault or output short circuit
Continuous sounding
Sounding (three beeps) every 5 seconds
Battery over charge
SPECIFICATIONS
Model Numbers
Capacity
PW5110 350A
350 VA / 210W
PW5110 500A
500 VA / 300W
PW5110 700A
700 VA / 420W
PW5110 1000A
1000 VA / 600W
PW5110 1500A
1500 VA / 900W
Nominal Output Voltage
240Vac
240Vac
Nominal Input Voltage
15%
Automatic Voltage Regulation (AVR)
50 / 60 Hz auto sensing
Frequency
6 Outlets (3 Battery Backup & Surge Protection;
Outlets
3 Surge Protection only)
Lighting / Surge Protection
476 Joules
Transfer time to Battery/AC
6ms typical
Battery Type
Maintenance free lead-acid battery
350 VA: 12V 4.5 Ah
500 VA: 12V 5 Ah
Battery Specification
750 VA: 12V 7 Ah
1000 VA: (2) 12V 7 Ah x 2
1500 VA: (2) 12V 9 Ah x 2
Typical Backup Time
3 MINUTES MINIMUM AT FULL RATED LOAD
LAN / Phone / Fax Protection
RJ11
Short Circuit Protection
Circuit Breaker
Communication Port
USB
Operation Temperature
0 C~40 C
Operation Relative Humidity
0 to 95% non-condensing
Storage Temperature
-15 C~50 C
350 VA: 5.9 kg
500 VA:6.1 kg
Net Weight
700 VA: 7.5 kg
1000 VA: 13.2 kg
1500 VA: 13.7 kg
350/500/700 VA: 270 x 87 x 259mm
Dimensions (HxWxD)
1000/1500 VA: 270 x 87 x 384mm
* Due to continuing product improvement programs, specifications are subject to change
without notice.
TROUBLESHOOTING
Symptom
Possible Cause
Action to Take
UPS will not turn on
The UPS is not connected
Ensure the UPS is securely
to the power source.
connected to an AC outlet.
Circuit Breaker has
Reduce the amount of equipment
tripped.
plugged into the "Battery Backup &
Surge Protection" outlets of the
UPS. Reset the circuit breaker by
pushing it back in. Switch the UPS
back on.
The "Battery Backup &
Turn off the UPS and reduce the
UPS is making a
Surge Protection" outlets
amount of equipment connected to
continuous sound and the
are overload.
these outlets.
"Overload" indicator is on
UPS does not provide
The UPS battery is
Charge the battery for 8 hours. The
discharged due to a power
UPS runtime is reduced until the
expected runtime
outage and has not
battery is fully charged.
recharged.
Devices plugged into Back
Unplug non-essential equipment
up & surge protection
(printers, scanners, etc) from the
receptacles exceed the
Battery Backup outlets and plug
into 'Surge Only' outlets
rated load for the UPS run
time
The UPS circuit breaker
Disconnect non-essential equipment
UPS does not power
tripped .
from the UPS. Reset (push in) the
essential equipment
circuit breaker and switch the UPS on.
during an outage
Plug equipment in one-at-a-time. If
the circuit breaker trips again,
disconnect the device that caused the
breaker to trip.
The battery has reached
Replace the battery or the battery
the end of its life.
module.
Equipment plugged into a
Unplug device from 'Surge Only' outlet
Surge Only outlet.
and move to a 'Battery Backup outlet.
Contact Technical Support (see
Red LED Indicator ON
Internal UPS fault.
Service and Support below).
SERVICE AND SUPPORT
For service and support please call your local distributor or the Powerware
Australia National Service and Repair Centre.
Australia freecall
1300 303 059.
Please have the following information ready:
Model number and serial number
Symptoms of failure or problem
Customer contact information
For additional information and to register your warranty, please visit
www.powerware.com.au
Register your warranty within 30 days and receive an extended pro-rated
warranty and load protection guarantee.
Eaton Power Quality Pty Ltd
119-127 Wicks Road,
North Ryde NSW 2113
MA6B412008(2005/01/20)