12
Installation in pipes (take fork position and marking into consideration)
Screwing in the device
• Turn by the hex bolt only, 15 to 30 Nm (11 to 22 lbf ft)
• Do not turn at the housing!
1.
13
Screwing in the device
Aligning the cable entry
1.
14
Housing with external locking screw and drip loop
The locking screw is not tightened when the device is delivered.
1. Loosen the external locking screw (maximum 1.5 turns).
2. Turn the housing, align the cable entry.
Avoid moisture in the housing, provide a loop to allow moisture to drain off.
3. Tighten the external locking screw.
5.3
Sliding sleeves
For more details, see the "Accessories" section.
A
2.
2.
Mounting
3.
4 3.5 Nm
A0034851
A0034852
A0037347