colored white, black, green, and red but not necessary
provided notation is made on schematic to aid field
servicing of equipment. When sourcing extension cable,
consideration should be given towards Belden 83754 for
14 AWG or equivalent as suitable. The inner foil shield
and the outer braid shield should be grounded as close
as possible to the EXV module in the control cabinet.
The expansion valve wiring cannot run in conduit with
other wiring that is over 24 Volts AC.
6. A flow switch must be installed in the leaving chilled
water line per manufacturer's instructions and wired to
Figure 54: Piping Schematic, Remote Evaporator (One of Two Circuits)
BALL
CHARGING
VALVE
VALVE
CHARGING
VALVE
SCHRADER
VALVE
RELIEF
VALVE
CHECK
VALVE
SCHRADER
VALVE
FIELD
CONNECTION
POINT
LIQUID
PIPING
FILTER
DRYER
FIELD INSTALLED LIQUID LINE COMPONENTS
CONDENSER
ASSEMBLY
CHARGING
BALL
VALVE
FILTER
VALVE
DRYER
ECON.
TRANSDUCER
LIQUID
PIPING
SCHRADER
VALVE
CHARGING
VALVE
ECONOMIZER
CHECK
VALVE
www.DaikinApplied.com
Installation and Application Considerations - Remote Evaporators
CONDENSER
AIR
ASSEMBLY
FLOW
LIQUID
INJECTION
PIPING
SOLENOID
SCHRADER
EXPANSION
VALVE
VALVE
VALVE
(OPTIONAL)
AIR
FLOW
AIR
FLOW
TEMP. SENSOR
ECONOMIZER FLASH GAS TO COMPRESSOR INTERSTAGE
ECON.
EXV. VALVE
RELIEF
VALVE
SCHRADER
VALVE
FIELD
CONNECTION
SOLENOID
POINT
SCHRADER
FILTER
VALVE
VALVE
DRYER
(OPTIONAL)
FIELD INSTALLED LIQUID LINE COMPONENTS
terminals 8 and 23 on terminal block M5 in the chiller
control panel. See Unit Field Wiring Diagrams -
46
and
Figure 47.
splice a 4 conductor, shielded cable, with drain wire. This
cable needs to be a minimum of 22 AWG. Preferably the
conductors are colored white, black, blue, and brown but
not necessary provided notation is made on schematic
for field servicing of equipment. When sourcing cable,
consideration should be made towards Belden 8729,
8723, 9940, or equivalent as suitable.
DISCHARGE
SCHRADER
DISCHARGE
PIPING
VALVE
TRANSDUCER
RELIEF
VALVE
AIR
FLOW
DISCHARGE
OUTSIDE AIR
TEMP. SENSOR
TEMPERATURE
(WAA)
BALL
STRAINER
VALVE
WATER OUT
(WOE)
(WIE)
TEMP. SENSOR
TEMP. SENSOR
CHARGING
DX EVAPORATOR
VALVE
REMOTE CHILLER
WITH OPTIONAL ECONOMIZER
DISCHARGE
DISCHARGE
SCHRADER
TRANSDUCER
PIPING
VALVE
RELIEF
OUTSIDE AIR
VALVE
TEMPERATURE
(WAA)
DISCHARGE
TEMP. SENSOR
LIQUID
BALL
STRAINER
INJECTION
VALVE
PIPING
WATER OUT
(WOE)
TEMP. SENSOR
EXPANSION
CHARGING
DX EVAPORATOR
VALVE
VALVE
33
IOM 1242-8 • PATHFINDER
If additional length of cable is required,
OIL PRESS.
TRANSDUCER
WITH SCHRADER
SHUT-OFF
PRESSURE
SHUT-OFF
VALVE
VALVE
SWITCH
VALVE
F3/F4
COMPRESSOR
SOLENOID
VALVE
WATER IN
SUCTION
TEMP. SENSOR
OIL PRESS.
SHUT-OFF
TRANSDUCER
VALVE
SHUT-OFF
WITH SCHRADER
VALVE
VALVE
LOW
PRESSURE
SWITCH
F3/F4
COMPRESSOR
CHARGING
SOLENOID
VALVE
SCHRADER
FIELD
CONNECTION
POINT
SUCTION
PIPING
SUCTION
TRANSDUCER
WATER IN
(WIE)
TEMP. SENSOR
FIELD PIPING
SHOWN DASHED
SUCTION
TEMP. SENSOR
MODEL AWV CHILLERS
®
Figure
LOW
RELIEF
VALVE
CHARGING
VALVE
SCHRADER
VALVE
FIELD
CONNECTION
POINT
SUCTION
PIPING
SUCTION
TRANSDUCER
FIELD PIPING
SHOWN DASHED
RELIEF
VALVE
VALVE
VALVE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents