Daikin Pathfinder AWV Installation, Operation And Maintenance Manual page 13

Air-cooled screw chillers
Table of Contents

Advertisement

Case 3: Three or More Units, Side-by-Side
For most models, there must be a minimum of 8 feet between
any units placed side-by-side; however, performance may be
affected at this distance.
Figure 21
3 performance adjustments as the distance between units
increases. For AWV models with IWSE option, the minimum
distance between multiple units is 10 feet as measured from
the outer base rail of the unit and performance adjustments are
represented in
Figure 23 and Figure 24.
NOTE: Data in
Figure 21
to
with a unit on each side. See Case 2 adjustment
factors for the two outside units.
Figure 20: Three or More Units, Side-by-Side
Figure 21: Case 3 - Full Load Capacity Reduction
Full Load Capacity Reduction
6.5
5.5
4.5
3.5
2.5
1.5
0.5
8
12
Distance Between Units
AWV008
AWV016
AWV024
www.DaikinApplied.com
and
Figure 22
depict Case
Figure 24
is for the middle unit
16
AWV010
AWV012
AWV014
AWV018
AWV020
AWV022
AWV026
AWV028
AWV030
Installation and Application Considerations
Figure 22: Case 3 - Power Increase
8.5
7.5
6.5
5.5
4.5
3.5
2.5
1.5
0.5
8
AWV008
AWV016
AWV024
Figure 23: Case 3 - Full Load Capacity Reduction - IWSE
Option
Full Load Capacity Reduction
6.5
6.0
5.5
5.0
4.5
4.0
3.5
3.0
2.5
2.0
10
AWV012
AWV020
AWV028
Figure 24: Case 3 - Power Increase - IWSE Option
Full Load Power Increase
20
9.0
8.0
7.0
6.0
5.0
4.0
3.0
10
AWV012
AWV020
AWV028
13
IOM 1242-8 • PATHFINDER
Full Load Power Increase
12
16
Distance Between Units (ft)
AWV010
AWV012
AWV018
AWV020
AWV026
AWV028
12
16
Distance Between Units
AWV014
AWV016
AWV022
AWV024
AWV030
12
16
Distance Between Units (ft)
AWV014
AWV016
AWV022
AWV024
AWV030
MODEL AWV CHILLERS
®
20
AWV014
AWV022
AWV030
20
AWV018
AWV026
20
AWV018
AWV026