Daikin Pathfinder AWV Installation, Operation And Maintenance Manual page 48

Air-cooled screw chillers
Table of Contents

Advertisement

Economizer EXV Module
Table 25: Analog Inputs
#
Description
S1
Economizer Pressure Circuit #1
S2
Economizer Temperature Circuit #1
S3
Economizer Pressure Circuit #2
S4
Economizer Temperature Circuit #2
Table 26: EXV Stepper Outputs
Driver
Description
A
Economizer EXV Circuit #1
B
Economizer EXV Circuit #2
Alarm/Limit Module
Table 27: Analog Inputs
#
Description
X3
Demand Limit
AC X7
Waterside Economizer Valve 1 Position
AC X8
Waterside Economizer Valve 2 Position
Table 28: Analog Outputs
#
Description
AC X2
Waterside Economizer Valve 1 Position
Command
AC X4
Waterside Economizer Valve 2 Position
Command
Table 29: Digital Inputs
#
Description
X1
External Alarm
X5
Circuit #1 Switch
X6
Circuit #2 Switch
DI1
Waterside Econ Enable
Table 30: Digital Outputs
#
Description
DO1
Evaporator Water Pump 2
DO2
Waterside Economizer Status
DO3
Circuit #1 Fan Output #5
DO4
Circuit #1 Fan Output #6
DO5
Circuit #2 Fan Output #5
DO6
Circuit #2 Fan Output #6
IOM 1242-8 • PATHFINDER
Signal Source
Ratiometric 0.5-4.5 Vdc
NTC 10K Thermister
Ratiometric 0.5-4.5 Vdc
NTC 10K Thermister
Signal Source
4 to 20 mA
4 to 20 mA
4 to 20 mA
Signal Source
4 to 20 mA
4 to 20 mA
Signal Off
Signal On
External Device
External
Failure
Device OK
Circuit Off
Circuit On
Circuit Off
Circuit On
Disable
Enable
Output Off
Output On
Pump Off
Pump On
Inactive
Active
Fan(s) Off
Fan(s) On
Fan(s) Off
Fan(s) On
Fan(s) Off
Fan(s) On
Fan(s) Off
Fan(s) On
MODEL AWV CHILLERS
®
RapidRestore
Module
®
Table 31: Digital Inputs
#
Description
DI1
RapidRestore
Unlock
DI2
Backup Chiller
Compressor VFDs
Table 32: Digital Inputs
#
Description
H1-S6
Circuit # Mechanical High
Pressure Switch
CN13-1
NOTE: Signal name is compressor model dependent.
Waterside Economizer Module
Table 33: Analog Inputs
#
Description
UC X1 Waterside Economizer EWT
Table 34: Digital Inputs
#
Description
AC DI1
Waterside Economizer Enable
Table 35: Digital Outputs
#
Description
AC DO2
Waterside Economizer Status
48
Controller Operation
Signal Off
Signal On
Lock Out Option
Unlock Option
Normal Chiller
Backup Chiller
Signal Off
Signal On
Alarm
No Alarm
Signal Source
NTC 10k
Thermistor
Signal Off
Signal On
Disable
Enable
Signal Off
Signal On
Inactive
Active
www.DaikinApplied.com