Download Print this page

IMO Jaguar VXM Instruction Manual page 126

Advertisement

U48 Input phase loss protection
This function selects operation of input phase
loss or power supply imbalance protection.
U 4 8
U S E R
Setting range : 0 to 2
Set value
0
Active (without reactor (ACR/DCR))
1
Active (with reactor (ACR/DCR))
2
Inactive
When "2" is set to U48, protection
against input phase loss or power
supply voltage imbalance is disabled.
In the event of a phase loss, the DC
capacitors will be stressed.
Failure may result.
U48 RS485 protocol selection
The protocol of RS485 communication is
changed.
U 4 9
U S E R
Setting range : 0, 1
Set value
0
FGI-bus (default)
1
Modbus-RTU
Separate instruction manual is available
detailing
communication
Contact IMO for details.
5-70
4 8
Operation
4 9
Operation
protocol,
etc.
U56 Speed agreement/PG error
(Detection width)
U57 Speed agreement/PG error
(Detection timer)
U58 PG error selection
These functions are effective for the option
card ( VXMEFC / OPC-G11S-PG, -PG2,
-PGA ).
Refer to each option card's instruction
manual.
U 5 6
U S E R
U 5 7
U S E R
U 5 8
U S E R
U59 Braking - resistor function select
When function code F13 (electronic thermal)
is set to 2, both the type of the braking resistor
and connection circuit are set. Factory setting
is set to nominal applied resistor and the
number of resistor is one. When the power
load capacities of resistor are increased, set
the factory setting properly.
U 5 9
U S E R
Setting range : 0 to A8 (HEX)
Setting of ten's digit ( type selection )
Set
Applicable inverter
value
capacity (kW)
0
Standard applied resistor
6
0.4 and 0.75
7
1.5 and 2.2
8
4.0
9
5.5
A
7.5
The resistor data above is for 400V
VXM series only. Do not connect a
resistor of too low [Ω] value.
Failure may result.
122
5 6
5 7
5 8
5 9
Resistance
Capacity
Duty
[Ω]
[W]
cycle
[%ED]
10%
-
-
200
200
160
400
130
400
80
800
60
900
5 Function Selection

Advertisement

loading