In the plant: Electrically connecting the conductivity electrode/transmitter ......... 22 Connecting conductivity electrode LRG 16-4 ................. 22 Connecting conductivity electrode LRG 16-9 ................. 22 Connecting the LRGT 1.-.. conductivity transmitter ................ 22 LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
Page 3
Action against high-frequency interference ................... 33 Taking the LRR 1-50, LRR 1-51 out of service .................. 34 Disposal ............................. 35 UL components ..........................35 Declaration of Conformity Standards and directives ........................35 LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
How to use this Manual This Installation & Operating Manual describes the correct use of the LRR 1-50, LRR 1-51 conductivity controller. It applies to persons who integrate this equipment in control systems, install, bring into service, operate, maintain and dispose of this equipment. Anyone carrying out the above-mentioned activities must have read this Installation &...
Warning of a situation that may result in minor or moderate injury. ATTENTION ATTENTION Warning of a situation that results in damage to property or the environment. LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
(flushing interval Si) and opens for a certain time (flushing time Sd). After the flushing time, the valve is moved into the OPERATING position or into the required control position. LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
Usage for the intended purpose The LRR 1-50, LRR 1-51 conductivity controller is used in combination with LRG 1.-.. conductivity electrodes and the LRGT 1.-.. conductivity transmitter as a conductivity controller and limit switch, e.g., in steam boilers and hot water installations or in condensate and feedwater tanks.
Check that the plant is not carrying live voltage before commencing work. ■ Faulty equipment is a danger to plant safety. If the LRR 1-50, LRR 1-51 conductivity controller does not behave as described on ■ this page, it may be faulty.
OPERATING position. If faults occur only in the LRR 1-50, LRR 1-51 conductivity controller, the MAX alarm is trig- gered, the continuous blowdown valve moves into OPERATING position and the system is restart- Parameters can be changed or the MAX alarm simulated by turning the rotary knob.
Approx. 0.44 lb (0.2 kg) Other information Incorporated type 1 action operating control Pollution degree 2, impulse voltage DC supply = 500 V, AC output = 2500 V LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
Tightening: Torque 0.79Nm or 7lb in. Use with accessory: LRGT 16-3, LRGT 16-4, LRGT 17-3 Rating plate of the LRR 1-51, bottom Rating plate of the LRR 1-50, bottom Fig. 1 LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
Take further measures to protect the equipment from lightning, insects and ■ animals, and salty air. You will need the following tools: Screwdriver size 1/8 in (3.2 mm) ■ LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
Installing the “LRR 1-52”50, “LRR 1-53”1 conductivity controller The LRR 1-50, LRR 1-51 conductivity controller is clipped onto a type TH 35, EN 60715 support rail in the control cabinet. Fig. 2 4 DANGER DANGER There is a risk of electric shock during work on electrical systems.
MAX output contact (switch-selectable) Supply voltage L2 Conductivity electrode LRG 16-4 (terminal 6/7: Supply voltage N a resistance thermometer can be connected) Central grounding point (CGP) in control cabinet LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
Supply voltage L2 customer Supply voltage N Actual value/manipulated variable output 4-20 mA (switch-selectable) Conductivity transmitter LRGT 1.-.., 4-20 mA, with grounding point Central grounding point (CGP) in control cabinet LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
Connected inductive loads must therefore have interference suppression (RC combination) as specified by the manufacturer. If used as a conductivity limiter, the LRR 1-50, LRR 1-51 conductivity controller does not interlock automatically when the MAX limit is exceeded.
UL 60730-1 between the current loop and live parts of the equipment that are not supplied with safety extra-low voltage (SELV). Attention Do not use unused terminals as support terminals. ■ Tools Screwdriver size 1/8 in (3.2 mm) ■ LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
This control cable is not UV-resistant and must be protected with a UV-resistant plastic tube or cable duct if installation is outdoors. For connection to the LRR 1-50 conductivity controller, please remove the connector and wire the terminal strip as shown in the wiring diagram. Fig. 3 Connect the shield to the central grounding point (CGP) in the control cabinet.
Set code switch c as shown in the table below. ■ Insert the lower terminal strip. ■ Switch the supply voltage back on. The equipment restarts. ■ Fig. 5 LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
* Controller software version 311178.13 or later Attention Do not move switches S1 and S2 on code switch c! Tools Screwdriver size 3.5 x 100 mm, fully insulated to VDE 0680-1. ■ LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
Faulty temperature sensor, temperature reading too high (LRR 1-50 only) E.005 Error Faulty measured value acquisition, reading too low E.006 Error Faulty measured value acquisition, reading too high LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
Or after 30 s, the actual value is displayed automatically. If password protection is enabled, you must enter the password before changing a parameter. See section on password protection. LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
The flushing interval is set between 0 and 24 hours. time. Select parameter Sd, enter and save the de- The flushing time is set between 1 and 4 minutes. sired time. LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
Page 28
CF value calculated on this basis. Press and hold the push- button (on rotary knob). CF value is outside the admissible range. The CF.Er previous calibration has been retained. LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
The flushing interval is set between 0 and 24 hours. time. Select parameter Sd, enter and save the The flushing time is set between 1 and 4 minutes. desired time. LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
TDS below the limit. The blowdown volume is established using the capacity charts of the continuous blowdown valve. Please refer to the Installation & Operating Manual for GESTRA continuous blowdown valves. LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
Once disabled, password protection is reactivated after 30 minutes of no activity (i.e., rotary knob is not turned), and the password must be entered again. The parameters are password-protected when the equipment is restarted, if password protection was previously enabled. LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
In the event of a fault in the conductivity controller, the MAX alarm is triggered and the equipment restarts. If the process repeats itself continuously, the equipment must be replaced. LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
Installation & Operating Manuals. If equalizing currents are likely (outdoor installa- tions), connect the shield on one side only. Suppress HF interference using hinged-shell ferrite rings. ■ LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
Detach the terminal strip. ■ Release the white slider holder at the bottom of the unit and detach the unit from the support rail. ■ Fig. 7 LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
Tel. +49 421 3503 0 +49 421 3503 393 e-mail info@de.gestra.com www.gestra.com Modifications to the equipment not approved by us will invalidate Declarations of Conformity and certificates. LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01...
Page 36
You can find our authorized agents around the world at: www.gestra.com GESTRA AG Münchener Straße 77 28215 Bremen Germany Tel. +49 421 3503 0 +49 421 3503 393 e-mail info@de.gestra.com www.gestra.com 850702-01/04-2022cm (809154-01) · GESTRA AG · Bremen...
Need help?
Do you have a question about the LRR 1-50 and is the answer not in the manual?
Questions and answers