O P E R A T I N G I N S T R U C T I O N S deTec4 Safety light curtain...
Page 2
Original document This document is an original document of SICK AG. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Operator of the machine................Design......................4.3.1 Scanning range and protective field width......8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 4
Reset to factory settings............Configuration mode.................. Configuring beam coding................. Configuring muting................... O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 5
11.3.3 Fault indicators................ 132 Decommissioning................139 12.1 Disposal..................... 139 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 6
16.3 Checklist for initial commissioning and commissioning......167 List of figures..................168 List of tables..................170 O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Data sheets and application examples • CAD data and dimensional drawings 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
The symbol indicates the sender. The symbol indicates the receiver. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Comply with the latest version of the applicable provisions on laser protection. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
You need suitable expertise and experience. You must be able to assess if the machine is operating safely. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
Page 11
For maintenance, you must be able to assess if the machine is operating safely. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
The safety light curtain has a resolution of 14 mm. This resolution provides finger protection. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
Diagnostic LEDs 7 and 8 light up if the bottommost beam (near system plug) is synchronized. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
The function can be configured during commissioning. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
• Switching on and off of the integrated laser alignment aid O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
The N-Mark is a trademark or registered trademark of NFC Forum, Inc. in the United States and in other countries. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 18
If a sender does not have an additional guest connected to it, the extension connection has no function and must be sealed with a protective cap. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
Page 19
SP2 system plug not suitable. An SP1 system plug must be used at the sender of a single system. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Connection of sender and receiver via a T-connector, shared 5-pin or 8-pin con‐ necting cable to the control cabinet O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
Safety light curtains with protective field height > 300 mm have multiple LEDs for the field indicator. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 22
Warning o LED off. Ö LED flashes. O LED illuminates. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 23
Further topics • "Diagnostic LEDs", page 124 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Figure 7: Hazardous point protection Figure 8: Access protection O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 25
Figure 10: Access protection with smart presence detection, implemented using cascade 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Overview This chapter contains important information about the design. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
The maximum protective field width is limited by the scanning range. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Machinery. SICK offers a stopping/run-down time measurement service in many countries. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 29
If the new value S is ≤ 500 mm, then use 500 mm. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 30
The greater value resulting from this comparison must be used. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
Figure 13: Minimum distance from reflective surfaces 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Calculate minimum distance a in millimeters (mm) based on the corresponding formula from table 13 table O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
2. This can disrupt the protective function of system 2. This would mean that the operator is at risk. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 34
In the case of systems in close proximity that are of a different type, take different measures to prevent mutual interference. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
Page 35
" is not affected by the infrared light from the sender !. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
In order to prevent mutual interference of systems, a sender with a small scanning range can be used. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
Page 37
"Data sheet", page 140 • "Ordering information", page 150 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
"Minimum distance from the hazardous point", page 28 • "Additional accessories", page 164 O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Calculating minimum distance without using a muting connector: • ≥ v × 0.060 s O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Once muting sensors A1 and A2 are actuated, muting is active. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 42
"Cross-circuit monitoring", page 46 • "Data sheet", page 140 O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 43
8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Exit monitoring is ended too early if one of the muting sensors remains clear for longer than 0.5 s, i.e. the sensor gap monitoring has been exceeded O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
Page 45
The total muting time is always active. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
The lower edge of the housing is flush with the transport level. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 48
(increased availability of the system). O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
2 consecutive objects and the objects have a minimum width of 10 mm ... 100 mm. The values depend on the object speed. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
Page 51
Objects on the transport level move into the hazardous area. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 52
Object exit (regardless of whether people can be ruled out on the transport level) or object entry (people can be ruled out on the transport level) O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
Page 53
If reset and Smart Box Detection Override are configured on the same input, both functions are started using a common control switch. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Figure 30: Dual-channel and isolated connection of OSSD1 and OSSD2 O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 55
Using the device in residential areas may cause radio interference. The operating entity is responsible for taking appropriate measures (e.g., shielding). 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
• A reset device, such as a reset pushbutton, is connected. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Positively guided contactors are used for shutting down the machine. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
During operation, the signal lamp indicates temporary muting or the detection of a valid object by Smart Box Detection. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
"Protection against interference from systems in close proximity to each other", page 33 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
If the sender and receiver are connected with each other, the laser alignment aid can also be activated by a command from IO-Link. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
Resolution and protective field heights of the individual systems may be different 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 62
Sender Receiver " Host § Guest 1 Guest 2 O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 63
Information regarding the maximum number of beams in a cascade can be found at Data sheet, page 140. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
The outputs (contacts 13-14 and 23-24) switch 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
H2 lamp flash. The system can be switched on. The system is enabled by pressing S1 (pushbutton is pressed and released). O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
The RLY3-OSSD2 is switched on by pressing S1 (pushbutton is pressed 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 68
If required, the restart interlock is implemented via the machine controller. • Mode of operation O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 69
OSSD1 safety relay. Operating mode: Without restart interlock, with external device monitoring. IO-Link: Data output via IO-Link connector. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 70
(optional). SELV/PELV safety extra-low voltage. • Task O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
"Test rod check", page Define all guidelines for the check. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Make sure that the outputs of the safety light curtain have no effect on the machine during the check of the components. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
Page 73
The field indicator must not light up green or flash yellow. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
After the test rod has been removed from the protective field, make sure that the protective field is clear and the field indicator is green or yellow. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
Use the system plugs provided. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 77
Torque 0.5 Nm ± 0.1 Nm. Figure 43: Mounting the system plug 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Notes on mounting Mount the sender and receiver on a level surface (!). O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 79
(§). § 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 80
O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
A screw nut or threaded hole is required on the machine or profile frame ($). 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Further topics • "Brackets", page 153 O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 83
Use an M5 screw to secure the position of the sender and receiver in the FlexFix bracket. (§) 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 84
Use an M5 screw to secure the position of the sender and receiver in the FlexFix bracket. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
• Mounting has been correctly executed. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
System connection (M12, 5-pin) Figure 51: System connection (male connector, M12, 5-pin) 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
OSSD1 (switching output 1) (laser alignment aid push‐ button) O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Pin assignment at the extension connection Figure 53: Extension connection (female connector M12, 5-pin) 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 90
Further topics • "Integration in electrical control", page 54 O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
SP1 system plug is used on all other receivers of the guest systems and on all senders. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
SP2 system plug. Then ensure the correct functioning of the device. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Table 31: Configurable functions when delivered Function Configuration when delivered Beam coding. Uncoded 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
2 rev.conf. Figure 56: Reset to factory settings O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
If the supply voltage is present for longer than 10 s, the safety light curtain changes to the locking state. Start again from step 1. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Beam coding does not have to be taken into account for the parity test. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
(row A) (row A) Muting deactivated (delivery condition) Cross muting 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
In cases where the actual protective field width is always at least 1 m, but may be less than 2 m, configure the dynamic protective field width (medium range). O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
Reduced resolution is only configured on the receiver of a single or host system. Prerequisites • SP2 system plug 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
The smart presence detection configuration is taken on by all guest devices in a cascade. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
• Single device with a resolution of 14 mm 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
The device is in configuration mode, the field indicator flashes green. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
The device can now be put into operation. To deactivate the external device monitoring, reset the receiver to the factory settings. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
The second device, guest 1, is connected to the host. The third device, guest 2, is connected to guest 1. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
The cascade can now be put into operation. Further topics • "Configuring beam coding", page 96 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Further topics • "Connection of sender and receiver", page 59 O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Make sure that the outputs of the safety light curtain do not affect the machine during the alignment process. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
LEDs 1 and 2 light up during alignment. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
• The sender and receiver are mounted with a QuickFix bracket O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
• Shift vertically • Rotate (± 15°) 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Carry out the checks specified in the test plan of the manufacturer of the machine and the operating entity. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Make sure that no dispersive media (e.g., dust, fog, or smoke) are within the calculated minimum distance from the protective field. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
Scanning range White adjustment is config‐ ured. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 118
Box Detection. The device is not in the Override required state. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 119
The sensor gap mon‐ itoring has been exceeded. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 120
O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 121
"Indication of the alignment quality", page 114 • "Diagnostic LEDs", page 124 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Make sure that the outputs of the safety light curtain do not affect the machine during the cleaning process. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
Carry out the checks specified in the test plan of the manufacturer of the machine and the operating entity. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Immediately after switching on, all LEDs on the sender and receiver briefly light up. Following this, the information below regarding configuration is indicated briefly. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
Page 125
Reduced resolu‐ White tion is configured. (3 s) 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 126
The topmost light beam (far from system plug) is Blue Blue synchronized. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Smart Box Detection is configured. Reduced resolution White is configured. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 128
Its own protective field is clear. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 129
Only Green the topmost beam is active. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 130
The protective field is Red/ interrupted. yellow The concurrence monitoring was exceeded. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 131
The protective field is low/r still interrupted after the expected object exit. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
"Fac‐ ÖÖ settings is activated. tory settings", page O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 133
"Ordering infor‐ mation", page 150. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 134
Switch the voltage supply off and back on again. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 135
Switch the voltage supply off and back on again. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 136
"Configuration", page O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 137
Check the wiring of the reset pushbut‐ ton. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 138
LED off. Ö LED flashes. O LED illuminates. Empty cells mean that the LED lights up, flashes, or is off. O P E R A T I N G I N S T R U C T I O N S | deTec4...
SICK will be glad to help you dispose of these devices on request. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
SILCL 3 (IEC 62061) (mean probability of a dangerous failure per hour) O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 141
The maximum permissible current must be observed. Calculation of number of beams: 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 142
(OSSDs) circuit monitored Response time "Response time", page 144 O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 143
1 Ω Cable between OSSD and load 2.5 Ω 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
80 ms applies regardless of the protective field height and beam coding. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
The response time of guest 1 within the cascade is t – 6 ms. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
≤ 10 m d ≤ 5 m ≤ 3 m O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 147
Control cabinet with safety relay or safety controller T-connector 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
1730 1740 2100 1860 1870 Tolerance: ± 50 g. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
1800 1812 1831 1950 1962 1981 2100 2112 2131 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
1220094 C4P-SA18011A00 1220121 C4P-EA18011C00 1950 1220095 C4P-SA19511A00 1220107 C4P-EA19511C00 O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 151
1220111 C4P-EA06011D00 1220112 C4P-EA07511D00 1220113 C4P-EA09011D00 1050 1220114 C4P-EA10511D00 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 152
1800 1220160 C4P-EA18031D00 1950 1220161 C4P-EA19531D00 2100 1220162 C4P-EA21031D00 O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
40,2 Figure 67: Dimensional drawing of the QuickFix bracket 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Make sure that all reflective surfaces and objects maintain the correct minimum distance from the protective field. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
Table 71: Weld spark guard ordering information Part Part number Weld spark guard 2069268 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Ambient operating temperature: Down to −30° C with fixed installation. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 157
Ambient operating temperature: Down to −30° C with fixed installation. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
1089796 Ambient operating temperature: Down to −30° C with fixed installation. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Unused. The connection is not required but may be present. 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Mounting To mount the deflector mirrors, use the included swivel mount brackets. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
1019424 1990 1950 PNS75-199 1092962 2140 2100 PNS75-214 1092963 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
1550 mm PU3H15-00000000 2068813 1740 mm 1720 mm PU3H17-00000000 2045643 O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Bracket for G6 muting sensor and P250 reflector 2113145 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
2101711 The information label cannot be used in applications with configured Smart Box Detection. O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
GB/T 19436.2 IEC 61496-3 GB 19436.3 IEC 61508 GB/T 20438 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 166
GB 28526 ISO 13849-1 GB/T 16855.1 ISO 13855 GB/T 19876 O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
46. Mounting the FlexFix bracket to a profile frame............83 47. Inserting the safety light curtain in the FlexFix brackets......... 84 O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
Page 169
74. Example of use of deflector mirrors................160 75. Recommended distance when using deflector mirrors.........161 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
45. LEDs on the receiver during normal operation............127 46. Fault indication on the sender.................132 O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK...
Page 171
99. Ordering details – cable cover for muting arm............164 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 172
100. Information label ordering information..............164 101. Note on standards....................165 O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 173
LIST OF TABLES 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 174
LIST OF TABLES O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK Subject to change without notice...
Page 175
LIST OF TABLES 8021645/1EB0/2022-04-28 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Subject to change without notice...
Page 176
E-Mail office@sick.com.gr E-Mail info@sick.ru Vietnam Hong Kong Singapore Phone +65 6744 3732 Phone +852 2153 6300 Phone +65 6744 3732 E-Mail sales.gsg@sick.com E-Mail ghk@sick.com.hk E-Mail sales.gsg@sick.com Detailed addresses and further locations at www.sick.com SICK AG | Waldkirch | Germany | www.sick.com...
Need help?
Do you have a question about the deTec4 and is the answer not in the manual?
Questions and answers