SiSG121917E
6.5
Drain System Abnormality
AF
Error Code
Method of Error
Water leakage is detected based on the float switch ON/OFF changeover while the compressor
Detection
is not operating.
Error Decision
The float switch changes from ON to OFF while the compressor is OFF
Conditions
Supposed
Error in the drain pipe installation
Causes
Defective float switch
Defective indoor unit PCB
Troubleshooting
Part 6 Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Are
the float switch and
the drain pipe
normal?
YES
Is the
water drain system
normal?
YES
Troubleshooting for MSP Duct Type Indoor Unit
NO
NO
The float switch may be
defective. Check if the
drain-up height and the
horizontal pipe length
exceed the specifications.
Clogged water drain
system, clogged drain
pump, or faulty float switch
Replace the indoor unit
PCB (control PCB). Check
if the drain-up height and
the horizontal pipe length
exceed the specifications.
(R24692)