Installation Checklist; Locating Your Gas Stove; Manufactured Mobile Home Additional Requirements; Combustion And Ventilation Air - Regency C34 Classic Owners & Installation Manual

Hide thumbs Also See for C34 Classic:
Table of Contents

Advertisement

installation
|
12
INSTALLATION
CHECKLIST
1. Locate your appliance. Refer to the following
sections:
a. Locating Your Classic Gas Stove
b. Clearances to Combustibles
c. Venting. See "Exterior Vent Terminal
Locations" to " Venting Arrangements"
sections.
2. Install Optional Fan. Refer to "Optional Fan
Installation" section.
3. Assemble stove base - pedestal or bottom shield
and legs. Refer to "Pedestal Assembly" or "Leg
and Bottom Shield Assembly" sections.
4. Choose a venting option and Install accordingly.
Refer to the following sections where applicable:
a. DV Stove Horizontal Vent Kit
b. Dura-Vent Termination kits
c. Vent Restrictor setting
d. Converting Class-A Metal Chimney or
Masonry Chimney to Direct Vent
System.
5. Make gas and electrical connections. Refer to
"Gas Connection" section. Test the pilot. Must
be as per Diagram in "Pilot Adjustment" section.
6. Install 4-AA batteries into receiver. This will
enable operation of appliance manually when
in "ON" position.
7. Test gas pressure. Refer to "Gas Pipe Pressure
Testing" section.
8. Install standard and optional features. Refer to
the following sections where applicable:
a. Log Installation
b. Door and Glass Frame
c. Door Handle
d. Safety Screen
e. Remote Control
f. Wall Thermostat
g. Install 1 AA battery into DC spark box
(See instructions in manual)
9. Final check. Refer to "Final Check" section.
12 |
Regency
®
CLASSIC™ C34-11 Direct Vent Freestanding Gas Stove
Before leaving this unit with the customer, the
installer must ensure that the appliance is fir-
ing correctly and operation fully explained to
customer.
This includes:
1. Clocking the appliance to ensure the correct
firing rate (rate noted on label) after burning
appliance for 15 minutes.
2. If required, adjusting the primary air to ensure
that the flame does not carbon. First allow
the unit to burn for 15-20 min. to stabilize.
3. Check for proper draft.
CAUTION: Any alteration to the product that
causes sooting or carboning that results in dam-
age is not the responsibility of the manufacturer.
LOCATING YOUR
GAS STOVE
When selecting a location for your stove, ensure
that the clearances on this page are met as well
as ensuring that there is adequate accessibility
for servicing and proper operation.
A)
Cross Corner
B)
Room Divider
C)
Island
D)
Flat on Wall
E)
Flat on Wall Corner
F)
Flush with Wall/Alcove
For Vent Termination requirements, see "Exterior
Vent Terminal Locations" section.
MANUFACTURED
MOBILE HOME
ADDITIONAL REQUIREMENTS
1. Ensure that structural members are not cut
or weakened during installation.
2. Ensure proper grounding using the #8 ground
lug provided. See "Optional Fan Installation"
section.
3. Appliance must be anchored to the floor. See
"Pedestal Assembly" & "Leg and Bottom"
sections.
COMBUSTION AND
VENTILATION AIR
The combustion air from this appliance is drawn from
outside the building through the outer flue. Extra
provision for combustion air is not required.
CLEARANCES TO
COMBUSTIBLES
The clearances listed below are MINIMUM dis-
tances. Measure the clearance to both the appliance
and the chimney connector. The farthest distance
is correct if the two clearances do not coincide.
For example, if the appliance is set as indicated
in one of the Diagrams but the back is too close,
move the stove until the correct clearance to the
back is obtained.
This unit can be installed on a solid combustible
surface like a wood floor. This unit can also be
installed directly on carpeting or vinyl when the
bottom pedestal cover plate (provided with the
unit) is installed.
This appliance may be installed only with the clear-
ances as shown in the situations pictured. Do not
combine clearances from one type of installation
with another in order to achieve closer clearances.
Use the minimum clearances shown in the Dia-
grams below:
C34 Clearance to Combustibles
A Side Wall to Unit
B Back Wall to Unit
E Side Wall to Unit
C34 Reference Dimensions
C Back Wall to Flue Centerline 13" / 330 mm
D Side Wall to Flue Centerline
F
Side Wall to Flue Centerline
Minimum ceiling height is 36" / 914 mm from top
of unit.
Minimum clearance to vent 1-1/4" (32 mm).
Back wall
B
C
A
D
Side wall
E
F
F
E
10" / 250 mm
6" / 150 mm
1.5" / 38 mm
22" / 559 mm
14" / 356 mm
A

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

C34-ng11C34-lp11

Table of Contents