Ducted Type Split Air-Conditioner Units(Inverter Series)
Selection of circuit breaker and power cord.
Model
FGR25Pd/DNa-M(O)
FGR30Pd/DNa-M(O)
FGR50Pd/D(2)Na-M(I)
FGR60Pd/D(2)Na-M(I)
NOTES!
① Selection of circuit breaker and power cord in the above table is based upon unit's
maximum power (maximum current).
② Specification of power cord is based on the working condition where ambient
temperature is 40℃ and multi-core copper cable (working temperature is 90℃, e.g.
power cable with YJV cross-linked copper, insulated PE and PVC sheath) is lying on
the surface of slot. If working condition changes, please adjust the specification
according to national standard.
③ Specification of circuit breaker is based on the working condition where ambient
temperature of circuit breaker is 40℃. If working condition changes, please adjust
the specification according to national standard.

4 Check Items After Installation and Test Operation

4.1 Check Items After Installation

Check items
Each part of the unit is installed securely?
Gas leakage test is taken or not?
Unit gets proper thermal insulation or not?
Drainage is smooth or not?
Is the voltage in accordance with the rated
voltage specified on the nameplate?
is the electric wiring and pipe connection
installed correctly?
Unit is securely grounded or not?
Power cord meets the required specification?
Is the air inlet/outlet blocked?
Length of refrigerant pipe and the charging
amount of refrigerant are recorded or not?
Binding pieces on compressor feet are
removed or not?
Power supply
380-415V 3N~ 50Hz
380-415V 3N~ 50Hz
380-415V 3N~ 50Hz
380-415V 3N~ 50Hz
Possible conditions due to improper installation.
Unit may have malfunction or components may get
Unit may have malfunction or components may get
Unit may have malfunction or components may get
The refrigerant charging amount is not accurate.
Circuit
Number of ground
breaker
wire × Min sectional
capacity
area (mm
(A)
25
1×2.5
32
1×4.0
10
1×1.5
10
1×1.5
Unit may drop, shake or emit noise.
Insufficient cooling (heating) capacity.
There may be condensation and dripping.
There may be condensation and dripping.
damaged.
damaged.
Electrical leakage.
damaged.
Insufficient cooling (heating) capacity.
Compressor may get damaged.
13
Number of power
cord × Min sectional
)
area (mm
)
2
2
4×2.5
4×4.0
4×1.5
4×1.5
Check