2.5 Installation of Wired Controller

Please refer to User Manual of Wired Controller for the installation details.
NOTICE!
When installation is finished, the unit must be tested and debugged before operation. Please
refer to Instruction Manual of ODU for auto addressing and debugging details.

2.6 Wiring Work

WARNING!
Before obtaining access to terminals, all supply circuits must be disconnected.
(1) Units must be earthed securely, or it may cause electric shock.
(2) Please carefully read the wiring diagram before carry out the wiring work, incorrect wiring could cause
malfunction or even damage the unit.
(3) The unit should be powered by independent circuit and specific socket.
(4) The wiring should be in accordance with related regulations in order to ensure the units reliable running.
(5) Install circuit breaker for branch circuit according to related regulations and electrical standards.
(6) Keep cable away from refrigerant pipings, compressor and fan motor.
(7) The communication wires should be separated from power cord and connection wire between indoor unit.
(8) Adjust the static pressure via wired controller according to site circumstance.
2.6.1 Connection of Wire and Patch Board Terminal
(1) The connection of wire (as shown in fig.13)
1) Strip about 25mm (1 inch.) insulation of the wire end by stripping and cutting tool.
2) Remove the wiring screws on the terminal board.
3) Shape the tail of wire into ring by needle nose plier, and keep the gauge of ring in
accordance with screw.
4) Use the screwdriver for tightening the terminal.
(2) The connection of stranded wire (as shown in fig.14)
1) Strip about 10mm (3/8 inch.) insulation of the end of stranded wire by stripping and
cutting tool.
Fig.12 Air-return Opening
Size of Air Outlet
A
B
347
1120
347
1120
7
Unit: mm
Size of Air –return Opening
C
D
1650
600
1650
755