Initial Start-Up - Carrier 19XR User Manual

Hermetic centrifugal liquid chillers 50/60 hz with pic ii controls and hfc-134a
Table of Contents

Advertisement

CHILLER EQUALIZATION WITH PUMPOUT UNIT —
The following steps describe how to equalize refrigerant pres-
sure on an isolated 19XR chiller using the pumpout unit.
1. Access the terminate lockout function on the CONTROL
TEST screen.
2.
IMPORTANT: Turn on the chilled water and con-
denser water pumps to prevent freezing.
3. Open valve 4 on the pumpout unit and open valves 1a and
1b on the chiller cooler and condenser, Fig. 29 and 30.
Slowly open valve 2 on the pumpout unit to equalize the
pressure. This process takes approximately 15 minutes.
4. Once the pressures have equalized, the discharge isola-
tion valve, cooler isolation valve, optional hot gas bypass
isolation valve, and the refrigerant isolation valve can be
opened. Close valves 1a and 1b, and all pumpout unit
valves.
Whenever turning the discharge isolation valve, be sure to
reattach the valve locking device. This prevents the valve
from opening or closing during service work or during
chiller operation.
The full refrigerant charge on the 19XR will vary with chill-
er components and design conditions, as indicated on the job
data specifications. An approximate charge may be determined
by adding the condenser charge to the cooler charge as listed in
Table 10.
Always operate the condenser and chilled water pumps
whenever charging, transferring, or removing refrigerant
from the chiller.
Use the CONTROL TEST terminate lockout function to
monitor conditions and start the pumps.
If the chiller has been shipped with a holding charge, the
refrigerant is added through the pumpout charging connection
(Fig. 29 and 30, valve 1b). First evacuate the nitrogen holding
charge from the chiller vessels. Charge the refrigerant as a gas
until the system pressure exceeds 35 psig (141 kPa) for
HFC-134a. After the chiller is beyond this pressure the refrig-
erant should be charged as a liquid until all the recommended
refrigerant charge has been added. The charging valve (Fig. 29
and 30, valve 7) can be used to charge liquid to the cooler if the
cooler isolation valve (11) is present and is closed. Do not
charge liquid through the linear float to the condenser.
TRIMMING REFRIGERANT CHARGE — The 19XR is
shipped with the correct charge for the design duty of the chill-
er. Trimming the charge can best be accomplished when the
design load is available. To trim the charge, check the tempera-
ture difference between the leaving chilled water temperature
and cooler refrigerant temperature at full load design condi-
tions. If necessary, add or remove refrigerant to bring the
temperature difference to design conditions or minimum
differential.
Table 10 lists the 19XR chiller refrigerant charges for each
cooler and condenser code. Total refrigerant charge is the sum
of the cooler and condenser charge.
Table 10 — Refrigerant (HFC-134a) Charge
REFRIGERANT
COOLER
CHARGE
CODE
lb
10
290
11
310
12
330
15
320
16
340
17
370
20
345
21
385
22
435
30
350
31
420
32
490
35
400
36
480
37
550
40
560
41
630
42
690
45
640
46
720
47
790
50
750
51
840
52
900
55
870
56
940
57
980
60
940
61
980
62
1020
65
1020
66
1060
67
1090
70
1220
71
1340
72
1440
75
1365
76
1505
77
1625
80
1500
81
1620
82
1730
85
1690
86
1820
87
1940

INITIAL START-UP

Preparation —
Before starting the chiller, verify:
1. Power is on to the main starter, oil pump relay, tower fan
starter, oil heater relay, and the chiller control panel.
2. Cooling tower water is at proper level and at-or-below
design entering temperature.
3. Chiller is charged with refrigerant and all refrigerant and
oil valves are in their proper operating positions.
4. Oil is at the proper level in the reservoir sight glasses.
5. Oil reservoir temperature is above 140 F (60 C) or above
refrigerant temperature plus 50° F (28° C).
6. Valves in the evaporator and condenser water circuits are
open.
NOTE: If the pumps are not automatic, ensure water is
circulating properly.
Do not permit water or brine that is warmer than 110 F
(43 C) to flow through the cooler or condenser. Refrigerant
overpressure may discharge through the relief valves and
result in the loss of refrigerant charge.
7. Access the CONTROL TEST screen. Scroll down on the
TERMINATE LOCKOUT option. Press the SELECT (to
enable the chiller to start) and answer YES to reset unit to
operating mode. The chiller is locked out at the factory in
order to prevent accidental start-up.
64
REFRIGERANT
CONDENSER
CHARGE
CODE
kg
lb
132
10
200
141
11
200
150
12
200
145
15
250
154
16
250
168
17
250
157
20
225
175
21
225
197
22
225
159
30
260
190
31
260
222
32
260
181
35
310
218
36
310
250
37
310
254
40
280
286
41
280
313
42
280
290
45
330
327
46
330
358
47
330
340
50
400
381
51
400
408
52
400
395
55
490
426
56
490
445
57
490
426
60
420
445
61
420
463
62
420
463
65
510
481
66
510
494
67
510
553
70
780
608
71
780
653
72
780
619
75
925
683
76
925
737
77
925
680
80
720
735
81
720
785
82
720
766
85
860
825
86
860
880
87
860
kg
91
91
91
113
113
113
102
102
102
118
118
118
141
141
141
127
127
127
150
150
150
181
181
181
222
222
222
190
190
190
231
231
231
354
354
354
420
420
420
327
327
327
390
390
390

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xrv19xrv

Table of Contents