19XR, XRV PIC II RAMP_DEM TABLE CONFIGURATION SHEET
DESCRIPTION
Pulldown Ramp Type:
Select: Temp=0, Load=1
Demand Limit + kW Ramp
Demand Limit Source
Select: Amps=0, kW=1
Motor Load Ramp% Min
Demand Limit Prop Band
Demand Limit At 20 mA
20 mA Demand Limit Opt
Motor Rated Kilowatts
Demand Watts Interval
DESCRIPTION
Control Point
ECW Control Option
Temp Pulldown Deg/Min
Temperature Reset
RESET TYPE 1
Degrees Reset At 20 mA
RESET TYPE 2
Remote Temp -> No Reset
Remote Temp -> Full Reset
Degrees Reset
RESET TYPE 3
CHW Delta T -> No Reset
CHW Delta T -> Full Reset
Degrees Reset
Select/Enable Reset Type
RANGE
0/1
0/1
5 to 20
3 to 15
40 to 100
0/1
50 to 9999
5 to 60
19XR, XRV PIC II TEMP_CTL TABLE CONFIGURATION SHEET
RANGE
0/1
2 to 10
–30 to 30
–40 to 245
–40 to 245
–30 to 30
0 to 15
0 to 15
–30 to 30
0 to 3
UNITS
%
%
DSABLE/ENABLE
kW
MIN
UNITS
DSABLE/ENABLE
ˆF
ˆF
DEG F
DEG F
ˆF
ˆF
ˆF
ˆF
CL-10
DEFAULT
VALUE
1
0
10
10
40
DSABLE
145
15
DEFAULT
VALUE
DSABLE
3
10
85
65
10
10
0
5
0