Carrier 19XR User Manual page 129

Hermetic centrifugal liquid chillers 50/60 hz with pic ii controls and hfc-134a
Table of Contents

Advertisement

19XR, XRV PIC II ISM_CONF TABLE CONFIGURATION SHEET
DESCRIPTION
Starter Type
(0=Full, 1=Red, 2=SS/VFD)
Motor Rated Line Voltage
Volt Transformer Ratio: 1
Overvoltage Threshold
Undervoltage Threshold
Over/Under Volt Time
Voltage% Imbalance
Voltage Imbalance Time
Motor Rated Load Amps
Motor Locked Rotor Trip
Locked Rotor Start Delay
Starter LRA Rating
Motor Current CT Ratio: 1
Current% Imbalance
Current Imbalance Time
Grnd Fault CT's?
Ground Fault CT Ratio: 1
Ground Fault Current
Ground Fault Start Delay
Ground Fault Persistence
Single Cycle Dropout
Frequency-60 Hz? (No=50)
Line Frequency Faulting
RANGE
UNITS
0 to 2
200 to 13200
VOLTS
1 to 35
105 to 115
%
85 to 95
%
1 to 10
SEC
1 to 10
%
1 to 10
SEC
10 to 5000
AMPS
100 to 60000
AMPS
1 to 10
cycles
100 to 60000
AMPS
3 to 1000
5 to 40
%
1 to 10
SEC
0/1
NO/YES
150
1 to 25
AMPS
1 to 20
cycles
1 to 10
cycles
0/1
DSABLE/ENABLE
0/1
NO/YES
0/1
DSABLE/ENABLE
CL-5
DEFAULT
VALUE
1
460
1
115
85
5
10
5
200
1000
5
2000
100
15
5
YES
150
15
10
5
DSABLE
YES
DSABLE