Carrier 19XR User Manual page 132

Hermetic centrifugal liquid chillers 50/60 hz with pic ii controls and hfc-134a
Table of Contents

Advertisement

DESCRIPTION
Capacity Control
Proportional Inc Band
Proportional DEC Band
Proportional ECW Gain
Guide Vane Travel Limit
Diffuser Control
Diffuser Option
Guide Vane 25% Load Pt
Diffuser 25% Load Point
Guide Vane 50% Load Pt
Diffuser 50% Load Point
Guide Vane 75% Load Pt
Diffuser 75% Load Point
Diffuser Full Span mA
VFD Speed Control
VFD Option
VFD Gain
VFD Increase Step
VFD Minimum Speed
VFD Maximum Speed
VFD Current Limit
19XR, XRV PIC II SETUP2 TABLE CONFIGURATION SHEET
STATUS
2 to 10
2 to 10
1 to 3
30 to 100
0 to 1
0 to 78
0 to 100
0 to 78
0 to 100
0 to 78
0 to 100
15 to 22
0/1
0.1 to 1.5
1 to 5
65 to 100
90 to 100
0 to 99999
UNITS
%
DSABLE/ENABLE
%
%
%
%
%
%
mA
DSABLE/ENABLE
%
%
%
Amp
CL-8
DEFAULT
VALUE
6.5
6.0
2.0
80
DSABLE
25
0
50
0
50
0
18
DSABLE
0.75
2
70
100
250