GENERATOR
Model
Rated Max. Continuous
Power Capacity (Watts*)
Rated Voltage
Rated Max. Continuous
Load Current (Amps)
120 Volts**
240 Volts
Main Line Circuit Breaker
Phase
Number of Rotor Poles
Rated AC Frequency
Power Factor
Recommended
Air Filter
Battery Requirement
(At 0° F -17.8 ° C)
Weight
Output Sound Level @ 23 ft (7m) at full load
Normal Operating Range
ASPAS1 CCA007
6,000 NG/7,000 LP
120/240
ASPAS1CCA012
12,000 NG/12,000 LP
120/240
ASPASICCA015
13,000 NG/15,000 LP
120/240
50.0 NG/58.3 LP
100.0
25.0 NG/29.2 LP
50.0
30 Amp
1
2
60 Hz
1
Carrier Part # 0C8127
Group 26
12 Volts and
350 Cold-cranking
Amperes Minimum
375 Pounds
68 db (A)
NG/100.0 LP
108.3
NG/50.0 LP
54.2
50 Amp
1
2
60 Hz
1
Carrier Part # 0C8127
Group 26
12 Volts and
525 Cold-cranking
Amperes Minimum
470 Pounds
70.5 db (A)
-20°F (-28.8°C) to 104°F (40°C)
NG/125.0 LP
NG/62.5 LP
65 Amp
1
2
60 Hz
1
Carrier Part # 0C8127
Group 26
12 Volts and
525 Cold-cranking
Amperes Minimum
487 Pounds
71.5 db (A)
* Maximum wattage and current are subject to and timlted by such factors as fuel atu content, ambient temperature, altitude, engine power and condition, etc. Maximum power decreases about 3.5
percent for each 1000 feet above sea level: and also will decrease about 1 percent for each 6" O (10° F) above 16° C (60° F) ambient temperature.
** Load current values shown for 120 volts are maximum TOTAL values for two separate circuits. The maximum current in each circuit must not exceed the value stated for 240 volts.
1.5.2
ENGINE
Type of Engine
Number of Cylinders
Rated Horsepower
Displacement
Cylinder Block
Valve Arrangement
Ignition System
Recommended
Spark Plug
Spark Plug Gap
Compression
Ratio
Starter
Oil Capacity Including Filter
Recommended
Oil Filter
Recommended
Air Filter
Operating RPM
ASPASICCA007
GH-410
1
14.5 @ 3,600 rpm
410cc
Aluminum w/Cast
iron Sleeve
Overhead Valves
Solid-state w/Magneto
RC 14YC
0.76 mm (0.030 inch)
8.6:1
12 Vdc
Approx. 1.5 Qts
Carrier Part # 70185D
Carrier Part # 0C8127
3,600
ASPAS1CCA012
GT-990
2
30 @ 3,600 rpm
992cc
Aluminum w/Cast
iron Sleeve
Overhead Valves
Solid-state w/Magneto
RC12YC
0.508 mm (0.020 inch)
9.5:1
12 Vdc
Approx. 1.7 Qts
Carrier Part # 70185D
Carrier Part # 0C8127
3,600
ASPASlCCA015
GT-990
2
30 @ 3,600 rpm
992cc
Aluminum w/Cast
iron Sleeve
Overhead Valves
Solid-state w/Magneto
RC12YC
0.508 mm (0.020 inch)
9.5:1
12Vdc
Approx. 1.7 Qts
Carrier Part # 70185D
Carrier Part # 0C8127
3,600
1.6
SYSTEM SET LED
The "System
Set" LED
is lit when
all of the following
conditions
are true:
1.
The AUTO/OFF/MANUAL
switch is set to the AUTO
position.
2.
The utility voltage being supplied to the unit is being
sensed by the PCB. If the utility sense voltage is not
connected to the unit or if it is below 168 volts AC,
then the system
set light will flash rapidly. This
indicates that if the AUTO/OFF/
MANUAL switch is
placed in the Auto position, the generator will start.
3.
The "Not In Auto" dip switch is set to the OFF position
on the control board.
6
Carrier
4.
No alarms
are present,
for example,
low oil pressure,
high temperature,
etc.
1.7
FUEL REQUIREMENTS
AND RECOMMENDATIONS
With
LP
gas,
use
only
the
vapor
withdrawal
system,
This
type
of system
uses
the vapors
formed
above the liquid fuel in the storage
tank. The engine
has
been fitted with a fuel carburetion
system
that meets the
specifications
of the 1997 California
Air Resources
Board
for tamper-proof
dual fuel systems.
The unit will run on
natural
gas or LP gas, but it has been factory
set to run
on natural
gas.