Unpacking; Lifting The Generator; Specifications - Carrier ASPAS1CCL015 Owner's Manual

Liquid-cooled, prepackaged standby generators
Table of Contents

Advertisement

Figure 1.6 - Low Coolant Level Sensor
1.7.4
OVERSPEED SHUTDOWN
The Pre-pack circuit board on liquid cooled units
receives AC frequency (rpm) signals directly from the
stator AC power windings, via sensing leads S15 and
S16. Should AC frequency exceed about 72 Hz, cir-
cuit board action will automatically shutdown the
engine (Figure 1.7).
Figure 1.7 - Control Module Assembly
Circuit Board
J2
E
A
M14
M15
M5
M8
M M
M1 M1 M1 M1
M1 M1
M1 M1
M
Q7
C1
R1
U1
M10
SW1
BR1
U12
R56
CR1
R12
C4
Q1
U6
R11
R10
CR7
CR37
K4
Q4
K2
Q5
Q3
K3
K1
M9
Q13
M2
R55
CR41
2002 GENERAC POWER SYSTEMS, ASSY #076009A
*Rated power of generator is subject to and limit-
ed by such factors as ambient temperature, alti-
tude, engine condition, and other factors. Engine
power will decrease about 3% for each 1000 feet
above 3000 feet and will decrease an additional
1.5% for each 10°F above 77°F . Maximum output
power of the generator is limited by maximum
engine power.
1.7.5
PCB OPERATION LED'S
• LED 1 is RED. The LED is ON when utility sensing
is NOT available to the circuit board. This LED will
function only when the AUTO/OFF/MANUAL switch
is set in the AUTO position.
• LED 2 is YELLOW. This LED is ON when the cir-
cuit board battery charger is on. This LED will
cycle ON and OFF with the battery charger, 4.85
hours on the 4.85 hours OFF.
6
Carrier
Section 1 — General Information
Carrier Liquid-cooled 15 kW Generators
PRE-PACKAGED STANDBY
U13
U14
U17
U15
C17
C18
C12
R68
R60
C21
C25
C22
U16
C3
C24
Q9
C2
C5
U2
C
U18
U3
U7
U9
Q12
U10
C23
Q2
C20
C8
Q11
C15
Q15
C10
C9
C 1
C11
LED2
U20
C14
C16
C7
Q6
C13
CUT R83
FOR 50HZ
• LED 3 is GREEN. This LED will flash when the cir-
cuit board has load voltage available to it. This
LED will function when voltage is available across
T1 and T2.
1.7.6
After 90 seconds of crank-rest cycles, this function
ends cranking if the engine fails to start in that
90-second span.
1.7.6
This clearly labeled fuse is located on the front panel
of the control system. It protects the panel wiring and
components from damaging overload. Always
remove this fuse before commencing work on the
generator. The unit will not start or crank if the fuse
is blown. Replace the fuse with one of the same size,
type, and rating. Carrier normally uses an AGC fuse
rated at 15 amps (part number 022676).
1.8
Handle shipping cartons and crates with care. Use
care to avoid damage from dropping, bumping, colli-
sion, etc. Store and unpack cartons with the proper
side up, as noted on the shipping carton.
M3
1.9
Q14
U5
U4
LED3
U19
When lifting or hoisting equipment is used, be
!
careful not to touch overhead power lines. The
generators weight of more than 900 pounds
C19
U8
requires proper tools, equipment, and qualified
personnel to be used in all phases of handling
Q16
and unpacking.
LED1
M4

1.10 SPECIFICATIONS

1.10.1 GENERATOR SPECIFICATIONS
Model ..................................................................ASPAS1CCL015
Phase ..................................................................................Single
Rated Max. Cont. AC Power Output (kW) ................................15
Rated Voltage (volts) ........................................................120/240
No. of Rotor Poles ......................................................................4
Driven Speed of Rotor ..........................................................1800
Rotor Excitation System ........................Direct excited brush type
Rotor/Stator Insulation ......................................................Class F
OVERCRANK SHUTDOWN
DC FUSE

UNPACKING

LIFTING THE GENERATOR