MAINTENENANCE
Section 3 -- Maintenance
Carrier Air-cooled 7 kW, 12 kW and 15 kW Generators
Figure 3.8 - Coofing Vent Locations
[]
D
t
°_
WARNING
/dRINTAKF
_The
exhaust from this product gets extremely
hot and remains hot after shutdown. High
grass, weeds, brush, leaves, etc. must remain
clear of the exhaust.
Such materials
may ignite
and burn from the heat of the exhaust system.
CAUTEON
_The
maximum ambient temperature
for the
generator
is 40 ° C (104 ° F).
3.9
CORROSION PROTECTION
Periodically
wash
and
wax
the
enclosure
using
automotive
type
products.
Frequent
washing
is
recommended
in salt water/coastal
areas. Periodically
spray all engine linkage parts and brackets with corrosion
inhibiting spray such as WD-40 or a comparable product.
3.10 ATTENTION AFTER SUBMERSION
If the
generator
has
been
submerged
in water,
it must
not be started
and operated.
Following
any
submersion
in water, have a Carrier Dealer thoroughly
clean and dry the generator.
3.11
OUT OF SERVICE PROCEDURE
3.11.1
REMOVAL FROM SERVICE
If the generator cannot be exercised every seven days,
and will be out of service longer than 90 days, prepare
the generator for storage as follows:
1.
Start the engine and let it warm up.
2.
Close the fuel shutoff valve in the fuel supply line and
allow the unit to shut down.
3.
Once the unit has shut down, it will signal a low oil
fault.
4.
Set the generator's main circuit breaker to its OFF (or
open) position.
5.
Set the AUTO/OFF/MANUAL
switch to OFF and turn
off the utility power to the transfer switch. Remove
the 7.5A and 15A fuses from the generator control
panel. Disconnect the battery cables as outlined in
"General Hazards" (page 2). Turn on the utility power
supply to the transfer switch in order to power the
emergency load centers circuits while utility power is
available.
6.
While the engine is still warm from running, drain the
oil completely.
Refill the crankcase
with oil. See
"Engine Oil Recommendations,"
Section 3.3.1.
7.
Attach a tag to the engine indicating the viscosity and
classification of the oil in the crankcase.
8.
Remove the spark plug(s) and spray fogging agent
into the spark plug(s) threaded openings. Reinstall
and tighten the spark plug(s).
9.
Remove the battery and store it in a cool, dry room
on a wooden board. Never store the battery on any
concrete or earthen floor.
10. Clean and wipe the entire generator.
3.11.2
RETURN TO SERVICE
To return the unit to service
after storage,
proceed
as follows:
1.
Verify that utility power is turned off and that the
AUTO/OFF/MANUAL
switch is set to OFF.
2.
Check the tag on the engine for oil viscosity and
classification.
Verify that the correct recommended
oil is used in the engine
(see Section
3.3.1).
If
necessary, drain and refill with the proper oil.
3.
Check
the state
of the battery.
Fill all cells
of
unsealed batteries to the proper level with distilled
water.
DO
NOT
USE
TAP
WATER
IN THE
BATTERY.
Recharge
the battery
to 100 percent
state of charge, or, if defective, replace the battery.
See "Specifications,"
Section 1.5, for type and size.
4.
Clean and wipe the entire generator.
5.
Remove the 7.5A and 15A fuses from the generator
control
panel.
Reconnect
the
battery.
Observe
battery polarity. Damage may occur if the battery is
connected incorrectly.
6.
Open the fuel shutoff valve.
7.
Insert the 7.5A and 15A fuses into the generator
control
panel.
Start
the
unit
by
moving
the
AUTO/OFF/MANUAL
switch to MANUAL. Allow the
unit to warm up thoroughly.
8.
Stop the unit by setting the AUTO/OFF/MANUAL
switch to OFF.
9.
Turn on the utility power to the transfer switch.
10. Set the AUTO/OFF/MANUAL
switch to AUTO.
11. The generator is now ready for service.
NOTE:
If the battery was dead or disconnected,
the exercise
timer must be reset,
1 6