Electric Characteristics - Haier AB072MRERA Service Manual

Table of Contents

Advertisement

3.6 Electric characteristics

Units
Model
Phase
AB072MRERA
1
AB092MRERA
1
AB122MRERA
1
AB162MRERA
1
AB182MRERA
1
AB242MRERA
1
AB282MRERA
1
AB302MRERA
1
AB382MRERA
1
AB482MRERA
1
AB602MRERA
1
Symbols:
MCA: Min. circuit amps (A)
MFA: Max. fuse amps of circuit breaker
Output: Fan motor rated output (w)
FLA: Full load amps (A)
Note:
1. Voltage range
The units are applicable for the electrical systems where voltage supplied to unit is in the range.
2. Maximum allowable voltage unbalance between phases is 2%.
3. MCA=1.25*FLA MFA≤4*FLA
4. Power supply uses the circuit breaker.
Volt.
FQY
Voltage
range
50/60
220
198~242
50/60
220
198~242
50/60
220
198~242
50/60
220
198~242
50/60
220
198~242
50/60
220
198~242
50/60
220
198~242
50/60
220
198~242
50/60
220
198~242
50/60
220
198~242
50/60
220
198~242
Power supply
Indoor fan motor
Output
MCA
MFA
(W)
0.39
1.24
22
0.39
1.24
22
0.39
1.24
22
0.39
1.24
22
0.39
1.24
22
0.39
1.24
36
0.39
1.24
36
0.71
2.28
63
0.71
2.28
63
0.71
2.28
78
0.71
2.28
78
47
Power input (w)
FLA
Cooling
Heating
0.31
30
30
0.31
30
30
0.31
30
30
0.31
30
30
0.31
30
30
0.31
50
50
0.31
50
50
0.57
90
90
0.57
90
90
0.57
110
110
0.57
110
110