Haier AB072MRERA Service Manual page 623

Table of Contents

Advertisement

(B) Definition and description of SW03
Set the
communication
and central
control address
SW03
by dip switch
(*Note 2)
Note 2:
• Set the address by dip switch when connecting the centralized controller or gateway or charge system.
• Address of centralized controller =communication address + 0 or +64.
SW03_ 2=OFF, address of centralized controller =communication address+0=communication address SW03_
2=ON, address of centralized controller=communication address+64 (applies when centralized controller is used
and there are more than 64 indoor units)
[1]
[2]
[3]
[4]
[5]
ON OFF OFF OFF OFF OFF OFF OFF
ON OFF OFF OFF OFF OFF OFF ON
ON OFF OFF OFF OFF OFF ON OFF
...
...
...
...
...
ON OFF ON ON ON ON ON ON
ON ON OFF OFF OFF OFF OFF OFF
ON ON OFF OFF OFF OFF OFF ON
ON ON OFF OFF OFF OFF ON OFF
...
...
...
...
...
ON ON ON ON ON ON ON ON
OFF ...
...
...
...
Communication
[6]
[7]
[8]
address
(default)
...
...
...
...
...
...
Set the address by wired controller
...
...
...
or automatically (default)
615
Central control
address
0
0
(default)
1
1
2
2
...
...
63
63
0
64
1
65
2
66
...
...
63
127