Haier AB072MRERA Service Manual page 240

Table of Contents

Advertisement

Indoor power supply wiring & signal wiring between indoor and outdoor & signal wiring between indoors.
Items
Cross
Section
Total
(mm
Current of
Indoor Units(A)
<7
2.5
≥7 and <11
4
≥11and <16
6
≥16 and <22
8
≥22 and <27
10
• The electrical power line and signal lines must be fastened tightly.
• Every indoor unit must have the ground connection.
• The power line should be enlarged if it exceeds the permissible length.
• Shielded lays of all the indoor and outdoor units should be connected together, with the shielded lay at the side of
signal lines of outdoor units grounded at one point.
• It is not permissible if the whole length of signal line exceeds 1000m.
Signal wiring of wired controller
Length of signal line (m)
≤ 250
※ The shielding lay of the signal line must be grounded at one end.
※ The total length of the signal line shall not be more than 250m.
Rated
Length
Current of
(m)
Overflow
2
)
Breaker(A)
20
10
20
16
25
20
30
32
40
32
Wiring dimensions
0.75mm
Rated current of residual
Circuit Breaker(A)
Ground Fault Interruptor(mA)
Response time(S)
10 A,30 mA,0.1S or below
16 A,30 mA,0.1S or below
20 A,30 mA,0.1S or below
32 A,30 mA,0.1S or below
32 A,30 mA,0.1S or below
2
×3 core shielded line
232
Cross Sectional
Area of Signal Line
Outdoor
Indoor
-indoor
-indoor
2
2
(mm
)
(mm
)
2 cores×(0.75-2.0)
2
mm
shielded line

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents