Haier AB072MRERA Service Manual page 588

Table of Contents

Advertisement

(3) Description of SW03
Set the
communication
and central
control address
SW03
by dip switch
(*Note 2)
Note 2
• The address must be set by dip switch if central control is used.
• SW03-2=OFF, central control address = physical address +0
• SW03-2=ON, central control address=physical address +64
• The address must be set by dip switch if 0151800113 and 0010451181A or 0151800086 are used together.
(4) Description of SW07
SW07_1
Tdiff correction valve in
SW07_2
AUTO mode
SW07_3
WIFI control mode
In heating, inlet air
SW07_4
temp. Tai correction
SW07_5
valve Tcomp2
Room card.
SW07_6
OEM HRV linkage
Operation mode
SW07_7
changeover of wired
SW07_8
controller
[1]
[2]
[3]
[4]
[5]
ON OFF OFF OFF OFF OFF OFF OFF
ON OFF OFF OFF OFF OFF OFF ON
ON OFF OFF OFF OFF OFF ON OFF
...
...
...
...
...
ON OFF ON ON ON ON ON ON
ON ON OFF OFF OFF OFF OFF OFF
ON ON OFF OFF OFF OFF OFF ON
ON ON OFF OFF OFF OFF ON OFF
...
...
...
...
...
ON ON ON ON ON ON ON ON
OFF ...
...
...
...
[1]
[2]
Tdiff correction valve in AUTO mode
OFF OFF
Tdiff: 0
OFF ON
Tdiff: 1
ON OFF
Tdiff: 2
ON
ON
Tdiff: 3 (default)
ON
One by one (defaulted)
OFF
One by multi
[4]
[5]
Inlet air temp. Tai correction valve Tcomp2 (EEPROM)
OFF OFF
Tai correction valve= 12°C
OFF ON
Tai correction valve= 5°C
ON OFF
Tai correction valve= 8°C
ON
ON
Tai correction valve=3°C (default)
ON
Room card is unavailable, HRV linkage is unavailable (default)
OFF
Room card is available, HRV linkage is available
[7]
[8]
Function
OFF OFF
[FAN] [COOL] [DRY] [HEAT]
OFF ON
[FAN] [COOL] [DRY]
ON OFF
[FAN] [COOL] [DRY] [HEAT] [ELECTRIC-HEAT]
ON
ON
[AUTO] [FAN] [COOL] [DRY] [HEAT](default)
Communication
[6]
[7]
[8]
address
(default)
...
...
...
...
...
...
Set the address by wired controller
...
...
...
or automatically (default)
580
Central control
address
0
0
(default)
1
1
2
2
...
...
63
63
0
64
1
65
2
66
...
...
63
127