11.6 Electric characteristics

Units
Model
Phase FQY Voltage Volt. range
AD182MMERA
1
AD242MMERA
1
AD282MMERA
1
AD302MMERA
1
AD382MMERA
1
AD482MMERA
1
Symbols:
MCA: Min. circuit amps (A)
MFA: Max. fuse amps of circuit breaker Output: Fan motor rated output (w) FLA: Full load amps (A)
Note:
1. Voltage range
The units are applicable for the electrical systems where voltage supplied to unit is in the range.
2. Maximum allowable voltage unbalance between phases is 2%.
3. MCA=1.25*FLA MFA≤4*FLA
4. Power supply uses the circuit breaker.
50/60
220
198-242
50/60
220
198-242
50/60
220
198-242
50/60
220
198-242
50/60
220
198-242
50/60
220
198-242
Power supply
Indoor fan motor
MCA
MFA
Output (W)
1.19
3.8
150
1.19
3.8
150
1.19
3.8
150
1.81
5.8
60/45
1.81
5.8
60/45
1.81
5.8
60/45
266
Power input (w)
FLA
Cooling
Heating
0.95
100
100
0.95
100
100
0.95
100
100
1.45
200
200
1.45
200
200
1.45
200
200