Electric wiring and the application

WARNING
• Switch off the main power switch of the indoor
and outdoor machine for more than 1 minutes
before the wiring or regular inspection.
• To prevent the destruction of wires and
electrical components by rats or other animals.
Serious, it may lead to the occurrence of fire.
• To avoid damage to the wire, avoid contact with
refrigerant pipes, steel edges and electrical
components. Serious, it may lead to the
occurrence of fire.
CAUTION
• Secure the power cord with a wire tie in the
machine.
Note:
when the wiring of the outdoor machine is not
using the wire, it should be fixed with the rubber
ring.
CAUTION
• In the case of 3 phase 5 wire type, the
power supply of the indoor machine must be
connected use L1 line and N line, prohibit the
use of L1-L2, L1-L3, Otherwise the electrical
part will be damaged.
Communication wiring figure
Indoor 3
P Q A B C
wired
A B C
controller
• To ensure that the electrical equipment used on the installation
• Check the power supply voltage in the range of 10% of the rated
• Check whether the power supply is satisfied. Otherwise, the
• By measuring the insulation resistance between the ground
• Connect the power cord to the terminal of the indoor unit and the
• Connect the external and internal communication lines to the
• Do not connect the fastening screws on the front of the cover.
• The power cord must be made of copper wire, and the power
• The power supply line is fixed with a round connection terminal
Outdoor
P Q
Indoor 4
P Q A B C
A B C
wired
controller
Inspect
site (main power switch, circuit breaker, wire, conduit and wiring
terminals, etc.) have been selected according to current data, to
ensure that the device in line with national standards.
voltage and the ground wire is included in the power supply line.
Otherwise, electrical parts will be damaged.
compressor will not start when the voltage is too low.
and the electrical device terminals, to ensure that more than 1
MΩ. Otherwise, the system can not be started until the cause of
leakage and maintenance.
Connection
outdoor mechanical and electrical gas box, connect the ground
wire to the grounding bolt of the outdoor machine and the indoor
mechanical and electrical air box.
1 and the 2 terminals on the terminal. If the power cord is
connected, the printed circuit board will be damaged. And the use
of shielded twisted pair wire.
supply must be in line with IEC 60245 requirements. If the power
cord length exceeds 20m, the need to increase the size.
with an insulating protective sleeve. Not with sheet metal contact
and extrusion, in order to avoid the cut line of skin caused by fire.
Indoor 1
P Q A B C
Indoor 5
P Q A B C
A B C
wired
controller
14
Communication wire with polarity
Indoor 2
P Q A B C
*
A B C
Indoor 6
P Q A B C
A B C
wired
controller
wired
controller
A B C
wired
controller