Model Number Legend; Specifications - Omron K3NC Manual

Up/down counting meter
Hide thumbs Also See for K3NC:
Table of Contents

Advertisement

K3NC

3 MODEL NUMBER LEGEND

Base Units
K3NC -
1
2 3 4
1, 2. Input Sensors Codes
NB: NPN inputs
PB: PNP inputs

Specifications

3 RATINGS
Supply voltage
Operating voltage range
Power consumption (See Note.)
Sensor power supply
Insulation resistance
Dielectric withstand voltage
Noise immunity
Vibration resistance
Shock resistance
Ambient
Operating
temperature
t
t
Storage
Ambient humidity
Operating
Ambient atmosphere
EMC
Approved standards
Weight
Note: An Intelligent Signal Processor with DC supply voltage requires approximately 1 A DC as control power supply current the moment
the Intelligent Signal Processor is turned on. Do not forget to take this into consideration when using several Intelligent Signal
Processors. When the Intelligent Signal Processor is not in measuring operation (e.g., the Intelligent Signal Processor has been
just turned on or is operating for startup compensation time), the display will read "ööööö" and all outputs will be OFF.
2
3. Supply Voltage
4. Display
1: 100 to 240 VAC
A: Basic Model
2: 12 to 24 VDC
C: Set Value LED Display
100 to 240 VAC (50/60 Hz); 12 to 24 VDC
85% to 110% of supply voltage
15 VA max. (max. AC load with all indicators lit)
10 W max. (max. DC load with all indicators lit)
80 mA at 12 VDC±10%
20 MΩ min. (at 500 VDC) between external terminal and case.
Insulation provided between inputs, outputs, and power supply.
2,000 VAC for 1 min between external terminal and case.
Insulation provided between inputs, outputs, and power supply.
±1,500 V on power supply terminals in normal or common mode ±1 µs, 100 ns for
square-wave noise with 1 ns
Malfunction: 10 to 55 Hz, 0.5-mm for 10 min each in X, Y, and Z directions
Destruction: 10 to 55 Hz, 0.75-mm for 2 hrs each in X, Y, and Z directions
2
Malfunction: 98 m/s
(10G) for 3 times each in X, Y, and Z directions
2
Destruction: 294 m/s
(30G) for 3 times each in X, Y, and Z directions
--10 to 55°C (14 to 131°F) with no icing
--20 to 65°C (--4 to 149°F) with no icing
25% to 85% (with no condensation)
Must be free of corrosive gas
Emission Enclosure:
Emission AC Mains:
Immunity ESD:
Immunity-RF-interference:
Immunity Conducted Disturbance: ENV50141:
Immunity Burst:
UL508, CSA22.2, CE; conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1);
conforms to VDE106/part 100 (Finger Protection) when the terminal cover is mounted.
Approx. 400 g
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61000-4-2:4-kV contact discharge (level 2)
8-kV air discharge (level 3)
ENV50140:
10 V/m (amplitude modulated, 80 MHz to
1 GHz) (level 3)
10 V/m (pulse modulated, 900 MHz)
10 V (0.15 to 80 MHz) (level 3)
EN61000-4-4:2-kV power-line (level 3)
2-kV I/O signal-line (level 4)