4. Control Registers (CR)

4.1 Table of Control Registers

CR#
Attribute
0
R
Model code
1
R
Firmware version
2
Group number triggered by
3
R/W
COM1 UD Link
Reference address of the data
4
R/W
senT through COM1 in UD
Link
Reference address of the data
5
R/W
received through COM1 in UD
Link
6
Group number triggered by
7
R/W
COM2 UD Link
Reference address of the data
8
R/W
sent through COM2 in UD Link
Reference address of the data
9
R/W
received through COM2 in UD
Link
10
R
Module status
11~19
R
Error Flag
20~27
R
UD Link status
28~29
Triggering the UD Link
30
R/W
sequence
Triggering the data exchange
31
R/W
through COM1 to read bits or
words
Triggering the data exchange
32
R/W
through COM2 to read bits or
words.
Triggering the data exchange
33
R/W
through COM1 to write bits or
words.
Triggering the data exchange
34
R/W
through COM2 to write bits or
words.
Selecting the "reading bits
35~36
R/W
through COM1" checkbox
Selecting the "reading words
37~38
R/W
through COM1" checkbox
DVP-PLC Operation Manual
Communication Module DVPSCM12/52-SL
Name of the register
Description
The code is set up by the system.
Model code of DVPSCM12-SL=H'4041
Model code of DVPSCM52-SL=H'4042
The firmware version is displayed in a hexadecimal value.
For example, H'0100 indicates that the firmware version is
V1.00.
Reserved
The group number triggered by COM1 UD Link
It is used when COM1 UD Link chooses "Base+Offset".
"Reference data register+Offset" defines the actual source
device for the data sending.
It is used when COM1 UD Link chooses "Base+Offset".
"Reference data register+Offset" defines the actual source
device for the data receiving.
Reserved
The Group number triggered by COM2 UD Link
It is used when COM2 UD Link chooses "Base+Offset".
"Reference data register+Offset" defines the actual source
device for the data sending.
It is used when COM2 UD Link chooses "Base+Offset".
"Reference data register+Offset" defines the actual source
device for the data receiving.
RUN or STOP
The flag for an error in the module
The execution status of UD Link
Reserved
0: Not triggered,
1~254: Number of times the UD Link sequence is
triggered
255: Always triggered
High byte: bit; Low byte: word
0: Not triggered; 1: Triggered once; 2: Always triggered
High byte: bit; Low byte: word
0: Not triggered; 1: Triggered once; 2: Always triggered
High byte: bit; Low byte: word
0: Not triggered; 1: Triggered once; 2: Always triggered
High byte: bit; Low byte: word
0: Not triggered; 1: Triggered once; 2: Always triggered
Bit = 0: Disabling the function of reading bits through
COM1.
Bit = 1: Enabling the function of reading bits through
COM1.
Bit = 0: Disabling the function of reading words through
COM1.
Bit = 1: Enabling the function of reading words through
COM1.
7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dvpscm12-slDvpscm52-sl